Wago

2252-1201

1 / 2
thumbnail
thumbnail
Part Number
2252-1201
Tariff Code
85369010000
UPC
4066966147131
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
24 A
Current at conductor cross-section (max.) mm²
32 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
5.2 mm / 0.205 inches
Height
36.5 mm / 1.437 inches
Depth from upper-edge of DIN-rail
30.8 mm / 1.213 inches

Material Data

Note (material data)
Information on material specifications can be found here
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.103 MJ
Weight
4.210 g

Mechanical Data

Mounting type
DIN-15 rail
Marking level
Center/side marking

Specifications

Product Group Code
0038

Commercial Data

Country of origin
DE
GTIN
4066966147131
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 20 ATEX 1013 U / IECEx: PTB 20.0029U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
22 A
Rated current (Ex e II) with jumper
20 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
20 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
20 A

Power Loss

Power loss, per pole (potential)
0.7661 W
Rated current IN for specified power loss
24 A
Resistance value for specified, current-dependent power loss
0.00133 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Push-button
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
1 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
1 … 2.5 mm² / 18 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
20 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
20 A

Related products