Wago
285-135
1 / 2
- Part Number
- 285-135
- Tariff Code
- 85369010000
- UPC
- 4045454507381
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 67 pcs.In-StockUpdated at: 21-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-1
- Nominal voltage (III/3)
- 1000 V
- Rated impulse voltage (III/3)
- 8 kV
- Rated current
- 125 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Physical Data
- Width
- 16 mm / 0.63 inches
- Height
- 86 mm / 3.386 inches
- Depth from upper-edge of DIN-rail
- 63 mm / 2.48 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Gray
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 1.257 MJ
- Weight
- 79.349 g
Mechanical Data
- Mounting type
- DIN-rail 35 x 15
- Mounting (note)
- Only suitable for DIN 35 x 15 rail
- Marking level
- Side marking
Specifications
- Product Group Code
- 0001
Commercial Data
- Packaging type
- Box
- Country of origin
- PL
- GTIN
- 4045454507381
- Customs tariff number
- 85369010000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 600 V
- Rated current CSA (Use Group B)
- 115 A
- Rated voltage CSA (Use Group C)
- 600 V
- Rated current CSA (Use Group D)
- 115 A
Power Loss
- Power loss, per pole (potential)
- 4.0625 W
- Rated current IN for specified power loss
- 125 A
- Resistance value for specified, current-dependent power loss
- 0.00026 Ω
Connection 1
- Connection technology
- POWER CAGE CLAMP
- Actuation type
- Operating tool
- Connectable conductor materials
- Copper
- Solid conductor
- 6 … 35 mm² / 8 … 2 AWG
- Stranded conductor
- 6 … 35 mm² / 8 … 2 AWG
- Fine-stranded conductor
- 6 … 35 mm² / 8 … 2 AWG
- Fine-stranded conductor; with insulated ferrule
- 6 … 35 mm² / 8 … 2 AWG
- Fine-stranded conductor; with uninsulated ferrule
- 6 … 35 mm² / 8 … 2 AWG
- Strip length
- 25 mm / 0.98 inches
- Wiring direction
- Side-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 600 V
- Rated current UL (Use Group B)
- 115 A
- Rated voltage UL (Use Group C)
- 600 V
- Rated current UL (Use Group C)
- 115 A