2-channel analog input; 0 ... 30 VDC; Differential input; Extreme
750-483/040-000
750-483/040-000
750-483/040-000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 50 Parts In-Stock from 9 Distributors

Additional Information

Part Number
750-483/040-000
UPC
4055143673105
Tariff Code
85389099990
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - analogue I/O module
Class Code : EC001596
Version : 7

Environmental Requirements

Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference
Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
8 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Physical Data

Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches

Material Data

Color
Dark gray
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.953 MJ
Weight
47.200 g
Conformity marking
CE

Technical Data

Number of analog inputs
2
Total number of channels (module)
2
Signal type
Voltage
Signal type (voltage)
0 … 30 VDC
Sensor connection
2 x (2-wire)
Input filter
Low pass (1st order), fG = 5 kHz
Signal characteristics
Differential
Resolution [bit]
14 bits
Data width
2 x 16-bit data; 2 x 8-bit control/status (optional)
Admissible continuous overload
60 V
Crosstalk attenuation
80 dB
Monotonicity without error code
Yes
Internal resistance
1000 kΩ
Conversion time (typ.)
1 ms
Measurement error (reference temperature)
25 °C
Measurement error, deviation (max.) from the upper-range value
0.1 %
Measurement error over entire temperature range
≤ 0.4 %
Temperature error (max.) of the upper-range value
0.01 %/K
Sampling duration
5 µs
Sampling delay (channel/channel)
1 µs
Sampling delay (module)
1 ms
Sampling repetition time
1 ms
Value of the least significant bit (LSB)
1.8 mV
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
80 mA
Dielectric strength
510 VAC/775 VDC; per EN 60870-2-1
Rated surge voltage
1 kV
Indicators
LED (A, E) green: Function AI 1, AI 2; LED (C, G) red: Error AI 1, AI 2

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143673105
Customs tariff number
85389099990

Related products