Wago

750-489

4-channel analog input; RTD/TC/Strain Gauge; 16 bits; Diagnostics; Intrinsically safe
750-489
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€659.60
1
Payment methods:
A total of 110 Parts In-Stock from 14 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€665.61

Additional Information

Part Number
750-489
UPC
4055143948029
Tariff Code
85389099990
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - analogue I/O module
Class Code : EC001596
Version : 7

Environmental Requirements

Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 … 2000 m / 0 … 6562 ft
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
Per EN 61000-6-2, marine applications
EMC emission of interference
Per EN 61000-6-3, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43

Connection Data

Connection technology: inputs/outputs
16 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Physical Data

Width
24 mm / 0.945 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches

Material Data

Housing material
Polycarbonate; polyamide 6.6
Fire load
2.036 MJ
Weight
99.300 g
Conformity marking
CE

Technical Data

Number of analog inputs
4
Total number of channels (module)
4
Signal type
Potentiometer positions || Thermocouple || Resistive temperature device || Resistors || MV encoder
Signal type (configurable)
Yes
Sensor connection
4 x (2-wire); RTD/R: 3-wire; 4-wire
Data width
4 x 16-bit data; 4 x 8-bit control/status (optional)
Resolution (over entire range)
0.1 K of full scale value; 0.01 K of full scale value (restricted to -50 °C … +150 °C)
Conversion time
≥10 ms/2 wires (per channel)*; ≥20 ms/3 wires, 4 wires (per channel)*; *for RTD/R; TC/U conversion time depends on module setting
Measurement error (25 °C)
In delivery state: ±0.2 % of the upper-range value (value achieved during calibration in operating environment 0 ≤ TA ≤ 55 °C); After user calibration: ±0.05 % of the upper-range value (only valid in the thermally stable operating state)
Temperature coefficient
±0.001 %/K of the upper-range value
Intrinsic safety Ex i
Yes
Measurement range
Resistive temperature devices: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Ni1000-TK5000; Resistors: 250 Ω, 500 Ω, 1 kΩ, 2 kΩ, 4 kΩ, PTC; Potentiometer setting: 0 … 100 %; Thermocouples: Type B (+250 … +1,820 °C); Type C (0 … +2,315 °C); Type E (-200 … +1,000 °C); Type J (-210 … +1,200 °C); Type K (-200 … +1,372 °C); Type N (-200 … +1,300 °C); Type R, S (-50 … +1,768 °C); Type T (-200 … +400 °C); mV sensors: ±30 mV; ±60 mV; ±120 mV; ±250 mV; ±500 mV; ±1,000 mV; ±2,000 mV; Thermistor: PTC; Resistor bridges (strain gauges): Uref: 2.4 V; Ud: ±15 mV, ±30 mV, ±60 mV
Cold junction compensation
Integrated
Configuration options
WAGO-I/O-CHECK || CODESYS Library || e!COCKPIT
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
60 mA
Supply voltage (field)
24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Current consumption, field supply (module with no external load)
120 mA
Power loss Pl
1.6 W
Isolation
Per EN/IEC 60079-11: 300 VAC system/supply; per EN/UL 61010-2-201: 1200 VDC system/supply/channel
Indicators
LED (A, C, E, G) green: Function AI 1 … AI 4; LED (B, D, F, H) red: Error AI 1 … AI 4
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Marking
ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143948029
Customs tariff number
85389099990

Notes

Note
The analog input module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!

Explosion Protection

Ex standard
EN IEC 60079-0, -7, -11
Safety-relevant data (circuit)
Uo = 4 V; Io = 13.46 mA; Po = 13.46 mW; linear characteristic curve
Reactances Ex ia IIC
Lo = 0.19 H; Co = 100 µF
Reactances Ex ia IIB
Lo = 0.78 H; Co = 1000 µF
Reactances Ex ia IIA
Lo = 1.57 H; Co = 1000 μF
Reactances Ex ia I
Lo = 2.57 H; Co = 1000 µF
Reactances (note)
Reactances, if the internal inductance Li or capacitance Ci (without cable) of the connected device is ≤1 % of the specified values.

Related products