Wago

750-535/040-000

1 / 4
thumbnail
thumbnail
thumbnail
thumbnail
Part Number
750-535/040-000
Tariff Code
85371098990
UPC
4055143649537
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - digital I/O module
Class Code : EC001599
Version : 7
€202.35
net
€213.00
Shipping from:
€35.00
1
Payment methods:
Best offer from:
NLTrusted Automa.Net Supplier
Availability:
50 pcs.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
02-04 December to United Kingdom
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environmental Requirements

Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3
Shock resistance
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 61373
EMC immunity to interference
Per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994
EMC emission of interference
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
8 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Physical Data

Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches

Material Data

Color
Blue
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.974 MJ
Weight
47.500 g
Conformity marking
CE

Technical Data

Number of digital outputs
2
Total number of channels (module)
2
Signal type
Digital
Signal type (voltage)
24 VDC
Actuator connection
2 x (2-wire)
Output characteristic
High-side switching
Switching frequency (max.)
1 kHz
Load type
Resistive, inductive, lamp load
Internal resistance Ri
285 Ω
Power consumption Pmax.
2.1 W (at 40 mA output current)
Output data width (internal) max.
2 bits
Intrinsic safety Ex i
Yes
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
7 mA
Supply voltage (field)
24 VDC; (Ex i XTR power supply: UO = max. 26.8 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Current consumption, field supply (module with no external load)
8.5 mA
Power loss Pl
1.1 W (at 40 mA output current)
Isolation
300 VAC system/field
Dielectric strength
510 VAC/775 VDC; per EN 60870-2-1
Rated surge voltage
1 kV; Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11)
Indicators
LED (A, E) green: Status DO 1, DO 2
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Current carrying capacity (power jumper contacts)
1 A
Marking
ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143649537
Customs tariff number
85371098990

Notes

Note
The digital output module must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 XTR manuals!

Explosion Protection

Ex standard
EN/IEC 60079-0, -7, -11
Safety-relevant data (circuit)
Uo = 26.8 V; Io = 99.91 mA; Po = 669.43 mW; linear characteristic curve
Reactances Ex ia IIC
Lo = 1.1 mH; Co = 0.092 µF
Reactances Ex ia IIB
Lo = 12 mH; Co = 0.72 µF
Reactances Ex ia IIA
Lo = 21 mH; Co = 2.37 µF
Reactances Ex ia I
Lo = 30 mH; Co = 3.85 µF
Reactances (note)
Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)

Related products