Wago
750-535/040-000
1 / 4
- Part Number
- 750-535/040-000
- Tariff Code
- 85371098990
- UPC
- 4055143649537
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Fieldbus, decentr. periphery - digital I/O module
- Class Code : EC001599
- Version : 7
€202.35
net€213.00
Shipping from:
€35.00
1
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 50 pcs.In-StockUpdated at: 21-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- 02-04 December to United Kingdom
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Environmental Requirements
- Ambient temperature (operation)
- -40 … +70 °C
- Ambient temperature (storage)
- -40 … +85 °C
- Protection type
- IP20
- Pollution degree
- 2 per IEC 61131-2
- Operating altitude
- Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
- Mounting position
- Horizontal (standing/lying); vertical
- Relative humidity (without condensation)
- 95 %
- Relative humidity (with condensation)
- Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- Vibration resistance
- Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3
- Shock resistance
- Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 61373
- EMC immunity to interference
- Per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994
- EMC emission of interference
- Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3
- Exposure to pollutants
- Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible H2S contaminant concentration at a relative humidity 75 %
- 10 ppm
- Permissible SO2 contaminant concentration at a relative humidity 75 %
- 25 ppm
Connection Data
- Connection technology: inputs/outputs
- 8 x CAGE CLAMP®
- Connection type 1
- Inputs/outputs
- Solid conductor
- 0.25 … 2.5 mm² / 24 … 14 AWG
- Fine-stranded conductor
- 0.25 … 2.5 mm² / 24 … 14 AWG
- Strip length
- 8 … 9 mm / 0.31 … 0.35 inches
Physical Data
- Width
- 12 mm / 0.472 inches
- Height
- 100 mm / 3.937 inches
- Depth
- 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail
- 60.6 mm / 2.386 inches
Material Data
- Color
- Blue
- Housing material
- Polycarbonate; polyamide 6.6
- Fire load
- 0.974 MJ
- Weight
- 47.500 g
- Conformity marking
- CE
Technical Data
- Number of digital outputs
- 2
- Total number of channels (module)
- 2
- Signal type
- Digital
- Signal type (voltage)
- 24 VDC
- Actuator connection
- 2 x (2-wire)
- Output characteristic
- High-side switching
- Switching frequency (max.)
- 1 kHz
- Load type
- Resistive, inductive, lamp load
- Internal resistance Ri
- 285 Ω
- Power consumption Pmax.
- 2.1 W (at 40 mA output current)
- Output data width (internal) max.
- 2 bits
- Intrinsic safety Ex i
- Yes
- Supply voltage (system)
- 5 VDC; via data contacts
- Current consumption (5 V system supply)
- 7 mA
- Supply voltage (field)
- 24 VDC; (Ex i XTR power supply: UO = max. 26.8 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Current consumption, field supply (module with no external load)
- 8.5 mA
- Power loss Pl
- 1.1 W (at 40 mA output current)
- Isolation
- 300 VAC system/field
- Dielectric strength
- 510 VAC/775 VDC; per EN 60870-2-1
- Rated surge voltage
- 1 kV; Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11)
- Indicators
- LED (A, E) green: Status DO 1, DO 2
- Number of incoming power jumper contacts
- 2
- Number of outgoing power jumper contacts
- 2
- Current carrying capacity (power jumper contacts)
- 1 A
- Marking
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I
Mechanical Data
- Mounting type
- DIN-35 rail
Specifications
- Product Group Code
- 0015
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4055143649537
- Customs tariff number
- 85371098990
Notes
- Note
- The digital output module must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 XTR manuals!
Explosion Protection
- Ex standard
- EN/IEC 60079-0, -7, -11
- Safety-relevant data (circuit)
- Uo = 26.8 V; Io = 99.91 mA; Po = 669.43 mW; linear characteristic curve
- Reactances Ex ia IIC
- Lo = 1.1 mH; Co = 0.092 µF
- Reactances Ex ia IIB
- Lo = 12 mH; Co = 0.72 µF
- Reactances Ex ia IIA
- Lo = 21 mH; Co = 2.37 µF
- Reactances Ex ia I
- Lo = 30 mH; Co = 3.85 µF
- Reactances (note)
- Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)