Wago

750-666/000-003

1 / 2
thumbnail
thumbnail
Part Number
750-666/000-003
Tariff Code
85371098990
UPC
4050821255475
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - digital I/O module
Class Code : EC001599
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Environmental Requirements

Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 … 2000 m / 0 … 6562 ft
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
Per EN 61000-6-2, marine applications
EMC emission of interference
Per EN 61000-6-4, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
16 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Physical Data

Width
24 mm / 0.945 inches
Height
100 mm / 3.937 inches
Depth
67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail
60.6 mm / 2.386 inches

Material Data

Housing material
Polycarbonate; polyamide 6.6
Fire load
2.021 MJ
Weight
111.000 g
Conformity marking
CE

Functional Safety

Achievable safety classes
SIL 3; Category 4, PL e
Safety standards
IEC 61508-1 … -7; EN ISO 13849-1; EN 62061
Test pulse duration (max.)
500 ms
Test pulse duration (min.)
0 ms

Technical Data

Number of digital inputs
4
Number of digital outputs
2
Total number of channels (module)
6
Signal type
Digital
Signal type (voltage)
24 VDC
Sensor connection
4 x (Fail-safe input with test pulse)
Actuator connection
2 x (fail-safe output with test pulse)
Input characteristic
Clock sensitive || Type 1
Input current per channel for signal (1) typ.
2.2 mA
Output circuit design
Power outputs
Output current per channel
10 A
Output current (module)
20 A
Output current
Short-circuit-protected
Switching frequency (max.)
50 Hz; Resistive load
Switching frequency (max.) (2)
0.1 Hz; Inductive load
Signal frequency (max.)
50 Hz
Load type of switching frequency
Resistive load
Configuration options
PROFIsafe address adjustable via DIP switch or engineering software
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
190 mA
Supply voltage (field)
24 VDC (-15 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Current consumption, field supply (module with no external load)
30 mA
Isolation
500 V system/field
Indicators
LED (A-D) green/red: Status/Error I1 … I4; LED (I-K) green/red: Status/error O1 … O2; LED (E) red: Group error; LED (F-H) green/red: Diagnostics
Number of incoming power jumper contacts
2
Number of outgoing power jumper contacts
2
Current carrying capacity (power jumper contacts)
10 A

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821255475
Customs tariff number
85371098990
End of Sale
2023-06-30
End of Production
2023-12-31
End of Delivery
2024-03-01
End of Service and Repair
2026-03-01