Wago

750-8206/040-000

1 / 2
thumbnail
thumbnail
Part Number
750-8206/040-000
Tariff Code
85371091990
UPC
4055143353618
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : PLC CPU-module
Class Code : EC000236
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Environmental Requirements

Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Relative humidity (without condensation)
95 %
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Mounting position
Horizontal (standing/lying); vertical
Mounting type
DIN-35 rail
Vibration resistance
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference
Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Fire load
3.303 MJ
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: communication/fieldbus
PROFIBUS: 1 x D-sub 9 socket; CANopen: 1 x D-sub 9 plug; Modbus (TCP, UDP): 2 x RJ-45; Modbus® RTU: 1 x D-sub 9 socket; RS-232 serial interface: 1 x D-sub 9 socket; RS-485 interface: 1 x D-sub 9 socket
Connection technology: system supply
2 x CAGE CLAMP®
Connection technology: field supply
4 x CAGE CLAMP®
Connection type 1
System/field supply
Solid conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor
0.25 … 2.5 mm² / 24 … 14 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches
Connection technology: device configuration
1 x Male connector; 4-pole

Physical Data

Width
112 mm / 4.409 inches
Height
100 mm / 3.937 inches
Depth
71.9 mm / 2.831 inches
Depth from upper-edge of DIN-rail
64.7 mm / 2.547 inches

Technical Data

Communication
PROFIBUS || CANopen || Modbus (TCP, UDP) || ETHERNET || EtherNet/IPTM Adapter (slave), library for e!RUNTIME || Modbus® RTU || RS-232 serial interface || RS-485 interface || MQTT
ETHERNET protocols
DHCP || DNS || NTP || FTP || FTPS || SNMP || HTTP || HTTPS || SSH
Visualization
Web-Visu
Operating system
Real-time Linux (with RT-Preempt patch)
CPU
Cortex A8; 600 MHz
Programming languages per IEC 61131-3
Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD) || Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
Programming environment
e!COCKPIT (based on CODESYS V3) || WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Configuration options
e!COCKPIT || WAGO-I/O-CHECK || Web-Based Management
Baud rate (communication/fieldbus 1)
10/100 Mbit/s
Baud rate
ETHERNET: 10/100 Mbit/s
Transmission medium (communication/fieldbus)
ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
Main memory (RAM)
256 MB
Internal memory (flash)
256 MB
Non-volatile hardware memory
128 KB
Program memory
CODESYS V2: 16 MB; CODESYS V3: 60 MB (Program and data memory (dynamically distributed))
Data memory
CODESYS V2: 64 MB; CODESYS V3: 60 MB Program and data memory (dynamically distributed)
Non-volatile software memory
128 KB || 128 KB
Type of memory card
SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO Memory Card)
Memory card slot
Push-push mechanism; cover lid (sealable)
Number of modules per node (max.)
64
Input and output process image (internal) max.
1000 words/1000 words
Input and output process image (Modbus®) max.
CODESYS V2: 1000 words/1000 words; CODESYS V3: 32000 words/32000 words
Input and output process image (PROFIBUS) max.
244 bytes/244 bytes
Input and output process image (CAN) max.
2000 words/2000 words
Indicators
LED (SYS, RUN, I/O, CAN, BF, DIA, U1 … U4) red/green/orange: Status system, program, internal data bus, CANopen, PROFIBUS, PROFIBUS diagnostics, status programmable by user (can be used via CODESYS library); LED (A, B) green: System power supply status, field supply
Derating
Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
Supply voltage (system)
24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed!
Input current (typ.) at nominal load (24 V)
550 mA
Power supply efficiency (typ.) at nominal load (24 V)
90 %
Current consumption (5 V system supply)
600 mA
Total current (system supply)
1700 mA
Supply voltage (field)
24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed!
Current carrying capacity (power jumper contacts)
10 A
Number of outgoing power jumper contacts
2
Ratings per
IEC/EN 60664-1
Rated surge voltage
1 kV

Mechanical Data

Weight
263.000 g
Color
Dark gray
Housing material
Polycarbonate; polyamide 6.6
Conformity marking
CE

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143353618
Customs tariff number
85371091990

Related products