- Communication
- PROFIBUS
- Visualization
- None
- CPU
- 16 bits
- Programming languages per IEC 61131-3
- Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD) || Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
- Programming environment
- WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
- Configuration options
- GSD device description file || WAGO-I/O-CHECK
- Cycle time
- < 3 ms for 1000 bit instructions/ 256 digital I/O
- Baud rate
- 9.6 kBd … 12 MBd
- Bus segment length (max.)
- 1200 m
- Transmission medium (communication/fieldbus)
- Cu cable per EN 50170
- Transmission time
- Typ. 1 ms (10 controllers; each 32 digital I/O and 12 Mbaud) max. 3.3 ms
- Number of fieldbus nodes on master (max.)
- 96
- Number of I/O points
- 6000
- Program memory
- 128 KB
- Data memory
- 64 KB
- Non-volatile software memory
- 8 KB
- Memory for fieldbus input variables (max.)
- 244 bytes
- Memory for fieldbus output variables (max.)
- 244 bytes
- Number of modules per node (max.)
- 63
- Input and output process image (fieldbus) max.
- 244 bytes/244 bytes
- Indicators
- LED (RUN) green: Fieldbus initialization, LED (BF, DIA, BUS) red: communication error, external diagnostics, configuration; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply
- Supply voltage (system)
- 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
- Input current (typ.) at nominal load (24 V)
- 500 mA
- Power supply efficiency (typ.) at nominal load (24 V)
- 87 %
- Current consumption (5 V system supply)
- 200 mA
- Total current (system supply)
- 1800 mA
- Supply voltage (field)
- 24 VDC (-25 … +30 %); via power jumper contacts
- Current carrying capacity (power jumper contacts)
- 10 A
- Number of outgoing power jumper contacts
- 3
- Isolation
- 500 V system/field
- Standard
- EN 50170