Wago

788-312

1 / 1
thumbnail
Part Number
788-312
Tariff Code
85364900990
UPC
4055143184137
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Switching relay
Class Code : EC001437
Version : 7
€8.73
net
€9.00
Shipping from:
€19.00
1
Payment methods:
Best offer from:
DKTrusted Automa.Net Supplier
Availability:
17 pcs.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
25-26 November to United Kingdom
Condition:
Used
Used - A previously used item with possible signs of cosmetic wear. It is fully operational and functions as intended, though the original packaging may be missing.
A total of 19 Parts In-Stock from 2 Distributors
Delivery from:
DK
DK
PL
PL
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (1)

788-312 product image
Condition:
Used
Available:
2 pcs.
In-Stock
Updated at: 21-11-2024
Offer from:
PLTrusted Automa.Net Supplier
Estimated Delivery:
25-26 November to United Kingdom
Warranty:
12 months
1
22,00 zł
net
Shipping from:
25,00 zł

Basic Relay

WAGO Basic Relay
788-156

Safety And Protection

Rated voltage
250 V
Rated surge voltage
4 kV
Pollution degree
3
Dielectric strength (control/load circuit) (AC, 1 min)
5 kVrms
Dielectric strength (open contact) (AC, 1 min)
1 kVrms
Dielectric strength (load/load circuit) (AC, 1 min)
2.5 kVrms
Safety information
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
Protection type
IP20

Load Circuit

Number of changeover/switchover contacts
2
Contact material (relay)
AgNi 90/10
Limiting continuous current
8 A
Inrush current (resistive) max.
(AC) 15 A / 4 s
Switching voltage (max.)
AC 250 V
Switching power (resistive) max.
AC 2000 VA; DC (see load limit curve)
Switching capacity
AC-15: 3 A / AC 250 V; DC-13: 2 A / DC 24 V
Recommended minimum load
12 V / 10 mA
Pull-in time (typ.)
8 ms
Drop-out time (typ.)
13 ms
Bounce time (typ.)
10 ms
Electrical life (NO; resistive load; 23 °C)
10 x 10³ switching operations
Mechanical life
30 x 10⁶ switching operations
Switching frequency with/without load (max.)
6 min-1 / 1200 min-1

Environmental Requirements

Ambient temperature (operation at UN)
-40 … +70 °C
Ambient temperature UL (operation at UN)
-40 … +50 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50 °C
Temperature range of connection cable
≥ (Tambient + 20 K)

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Control Circuit

Nominal input voltage UN
DC 24 V
Input voltage range
±10 %
Nominal input current at UN
19 mA

Physical Data

Width
15 mm / 0.591 inches
Height
86 mm / 3.386 inches
Depth from upper-edge of DIN-rail
54 mm / 2.126 inches

Material Data

Color
Gray
Fire load
1.357 MJ
Weight
45.540 g

Standards And Specifications

Standards/specifications
EN 61010-2-201 || EN 61810-1 || EN 61373 || UL 508

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
CN
GTIN
4055143184137
Customs tariff number
85364900990

Notes

Safety information
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
Note
Reinforced insulation between coil and contactsTo protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.

Signaling

Status indicator
Red LED

Related products