Wago

789-1341

1 / 2
thumbnail
thumbnail
Part Number
789-1341
Tariff Code
85364900990
UPC
4050821386728
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Switching relay
Class Code : EC001437
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Safety And Protection

Rated voltage
250 V
Rated surge voltage
4 kV
Pollution degree
2
Dielectric strength (control/load circuit) (AC, 1 min)
3.5 kVrms
Dielectric strength (open contact) (AC, 1 min)
1 kVrms
Protection type
IP20

Load Circuit

Number of changeover/switchover contacts
1
Contact material (relay)
AgNi
Limiting continuous current
12 A
Inrush current (resistive) max.
(AC) 30 A / 0.02 s; (AC) 24 A / 4 s
Switching voltage (max.)
AC 250 V
Switching power (resistive) max.
AC 3000 VA; DC (see load limit curve)
Recommended minimum load
12 V / 10 mA
Pull-in time (typ.)
15 ms
Drop-out time (typ.)
8 ms
Bounce time (typ.)
6 ms
Mechanical life
5 x 10⁶ switching operations

Environmental Requirements

Ambient temperature (operation at UN)
-25 … +50 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50 °C

Connection Data

Connection technology
CAGE CLAMP®
Solid conductor
0.2 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor
0.2 … 2.5 mm² / 24 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Control Circuit

Nominal input voltage UN
DC 24 V
Input voltage range
±10 %
Nominal input current at UN
17 mA

Physical Data

Width
17.5 mm / 0.689 inches
Height
90 mm / 3.543 inches
Depth from upper-edge of DIN-rail
55 mm / 2.165 inches

Material Data

Fire load
0.732 MJ
Weight
50.800 g

Standards And Specifications

Standards/specifications
EN 60664-1

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821386728
Customs tariff number
85364900990

Notes

Note
To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.

Signaling

Status indicator
Red LED