Wago
883-1204
1 / 2
- Part Number
- 883-1204
- Tariff Code
- 85369010000
- UPC
- 4055143940610
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-1
- Nominal voltage (III/3)
- 1000 V
- Rated impulse voltage (III/3)
- 8 kV
- Rated current
- 269 A
- Current at conductor cross-section (max.) mm²
- 290 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Continuous operating temperature
- -35 … +105 °C
Physical Data
- Width
- 27 mm / 1.063 inches
- Height
- 91 mm / 3.583 inches
- Depth from upper-edge of DIN-rail
- 90 mm / 3.543 inches
Material Data
- Note (material data)
- Information on material specifications can be found here
- Color
- Blue
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.000 MJ
- Weight
- 280.700 g
Mechanical Data
- Tightening torque
- 12 … 20 Nm
- Mounting type
- DIN-rail 35 x 7.5
- Marking level
- Side marking
Specifications
- Product Group Code
- 0001
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4055143940610
- Customs tariff number
- 85369010000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 600 V
- Rated current CSA (Use Group B)
- 228 A
- Rated voltage CSA (Use Group C)
- 600 V
- Rated current CSA (Use Group C)
- 228 A
- Rated voltage CSA (Use Group D)
- 600 V
- Rated current CSA (Use Group D)
- 228 A
Power Loss
- Power loss, per pole (potential)
- 8.6833 W
- Rated current IN for specified power loss
- 269 A
- Resistance value for specified, current-dependent power loss
- 0.00012 Ω
Connection 1
- Connection technology
- Screw connection
- Actuation type
- T-wrench; 6 mm
- Connectable conductor materials
- Copper || Aluminum
- Connectable conductor materials (note)
- Terminating Aluminum Conductors Both restrictions and application notes must be observed when terminating aluminum conductors. These instructions can be found in the WAGO Webshop under “Downloads – Documentation – Additional Information: Terminating Aluminum Conductors.”
- Nominal cross-section
- 120 mm²
- Solid conductor
- 16 … 150 mm² / 6 AWG … 300 kcmil
- Stranded conductor
- 16 … 150 mm² / 6 AWG … 300 kcmil
- Fine-stranded conductor
- 16 … 120 mm² / 6 AWG … 250 kcmil
- Fine-stranded conductor; with insulated ferrule
- 16 … 95 mm² / 6 … 3/0 AWG
- Strip length
- 27 mm / 1.06 inches
- Wiring direction
- Side-entry wiring
- Screw thread
- M10
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 600 V
- Rated current UL (Use Group B)
- 228 A
- Rated voltage UL (Use Group C)
- 600 V
- Rated current UL (Use Group C)
- 228 A
- Rated voltage UL (Use Group D)
- 600 V
- Rated current UL (Use Group D)
- 228 A