Wago
884-3000
1 / 2
- Part Number
- 884-3000
- Tariff Code
- 85369095000
- UPC
- 4055143941952
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Nominal voltage (III/3)
- 1000 V
- Rated impulse voltage (III/3)
- 8 kV
- Rated current
- 520 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Continuous operating temperature
- -40 … +120 °C
Physical Data
- Width
- 55 mm / 2.165 inches
- Height
- 164 mm / 6.457 inches
- Depth from upper-edge of DIN-rail
- 86 mm / 3.386 inches
Material Data
- Note (material data)
- Information on material data can be found here
- Color
- Beige
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.000 MJ
- Weight
- 510.000 g
Mechanical Data
- Tightening torque
- 25 … 60 Nm
- Mounting type
- DIN-35 rail || Panel mounting
Specifications
- Product Group Code
- 0001
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4055143941952
- Customs tariff number
- 85369095000
Power Loss
- Power loss, per pole (potential)
- 16.224 W
- Rated current IN for specified power loss
- 520 A
- Resistance value for specified, current-dependent power loss
- 6e-005 Ω
Connection 1
- Connection technology
- Bolt-type connection
- Actuation type
- Open-end, ring, socket wrench; 24 mm
- Connectable conductor materials
- Copper
- Nominal cross-section
- 300 mm²
- Clamping range
- 25 … 300 mm² / 6 AWG … 600 kcmil
- Type of cable lugs per DIN 46234
- Cable lugs for solder-free connectionsRing type, without insulating sleeve, for copper conductors
- DIN 46234: 1 cable lug per side
- 25 … 240 mm²
- DIN 46234: 2 cable lugs per side
- 50 … 240 mm²
- Type of cable lugs per DIN 46235
- Cable lugs for compression connectionsCover plate type for copper conductors
- DIN 46235: 1 cable lug per side
- 50 … 300 mm²
- DIN 46235: 2 cable lugs per side
- 50 … 240 mm²
- Thread size
- M16
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 1000 V
- Rated current UL (Use Group B)
- 420 A
- Rated current UL (Use Group B), factory wiring only
- 510 A
- Rated voltage UL (Use Group C)
- 1000 V
- Rated current UL (Use Group C)
- 420 A
- Rated current UL (Use Group C), factory wiring only
- 510 A