Description

Surge protection for instrumentation and control, 12 V, 500 mA, IEC 61643-21
Part Number
1064340000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Further Details Of Approvals

GOST certificate
GOST-Zertifikat

General Data

Colour
black
Design
Terminal
Isolating function
No
Optical function display
Yes
Protection degree
IP20
Rail
TS 35
Segment
Measurement - Monitoring - Setting
UL 94 flammability rating
V-0
Version
Surge protection for measurement and control

Probability Of Failure

Λges
54
MTTF
2,114 years
PFH in 1*10
1.8
SFF
96.67 %
SIL PAPER
SIL PAPER
SIL in compliance with IEC 61508
3

Approvals

Approvals
CE, CSAEX, EAC, FUSAFETY, OEVE, UL
ROHS
Conform
UL File Number Search
E311081

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
III

Rated Data Iec / En

Discharge current I
2.5 kA
Discharge current, max. (8/20 µs)
20 kA
Fuse
0.5 A
Insertion loss
732.08 kHz
Leakage current at U
3.2 mA
Lightning test current I
1 kA
Lightning test current, I
1 kA
Max. continuous voltage, Uc (DC)
15 V
Number of poles
1
Overload - failure mode
Modus 2
Protection level U
≤ 100 V
Pulse-reset capacity
≤ 20 ms
Rated current I
500 mA
Rated voltage (DC)
12 V
Requirements category acc. to IEC 61643-21
C2, C3, D1
Signal transmission properties (-3 dB)
750 KHz
Standards
IEC 61643-21
Surge current-carrying capacity C2
2.5 kA 8/20 µs
Surge current-carrying capacity C3
10 A 10/1000 µs
Surge current-carrying capacity D1
1 kA 10/350 μs
Voltage type
DC
Volume resistance
1.8 Ω 10 %

Dimensions And Weights

Width
6.2 mm
Width (inches)
0.244 inch
Height
88.5 mm
Height (inches)
3.484 inch
Depth
81 mm
Depth (inches)
3.189 inch
Net weight
46.2 g

Csa Protection Data

Gas group C
IIB
Gas group D
IIA
Gas groups A, B
IIC
Input current, max. I
500 mA
Input voltage, max. U
15 V
Internal capacity, max. C
2 nF
Internal inductance, max. L
0 µH

Connection Data

Type of connection
Screw connection
Tightening torque, min.
0.5 Nm
Tightening torque, max.
0.8 Nm
Clamping range, min.
0.5 mm²
Clamping range, max.
4 mm²
Wire cross-section, solid, min.
0.5 mm²
Wire cross-section, solid, max.
6 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
0.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
4 mm²
Connection cross-section, stranded, min.
0.5 mm²
Connection cross-section, stranded, max.
4 mm²

Rated Data Ul

Certificate No. (UL)
E311081
UL certificate
UL Zertifikat

Tender Specification Sheets

Long specification
Surge protection in a one piece, 6.2 mm wide DIN rail module for two binary, potential-free signal circuits with 12 V DC. Signal indication via a green LED. When the terminal is fitted, a simultaneous electrically conducting contact is made between the mounting rail (earth) and the reference potential (ground) of the protection circuit in the terminal. Optical identification of the terminal based on the type of protected switching and the voltage level. The terminal can be labelled or marked.
Short specification
Surge protection in a one piece, 6.2 mm wide DIN rail module for two binary, potential-free signal circuits. Signal indication via a green LED. Version: 12V DC

Classifications

ETIM 6.0
EC000943
ETIM 7.0
EC000943
EClass 9.0
27-13-08-07
EClass 9.1
27-13-08-07
EClass 10.0
27-13-08-07
UNSPSC
30-21-19-21

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Temperatures

Humidity
5...96 %
Operating temperature, max.
70 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
80 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...70 °C
Storage temperature
-40 °C...80 °C

Ratings Iecex/Atex/Cul

CUL certificate
cUL Certificate