Weidmuller

1070470000

1 / 3
thumbnail
thumbnail
thumbnail

Description

Surge protection, Flange-mounted housing, IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006
Part Number
1070470000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Further Details Of Approvals

GOST certificate
GOST-Zertifikat

Protection Ex - Data

ATEX - dust labelling
II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling
II 1 G Ex ia IIC T4… T6 Ga
Certificate No. (ATEX)
KEMA10ATEX0148X
IECEx - dust labelling
II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling
II 1 G Ex ia IIC T4… T6 Ga
Internal inductance, max. L
0 µH

General Data

Colour
Light Blue
Design
Terminal, miscellaneous
Optical function display
No
Protection degree
IP20
Rail
TS 35, TS 35 x 7.5
Segment
Measurement - Monitoring - Setting
UL 94 flammability rating
V-0
Version
Flange-mounted housing

Approvals

Approvals
CE, CSAEX, EAC, IECEXDEK, KEMAATEX
ROHS
Conform

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
III

Rated Data Iec / En

Dielectric strength at FG against PE
≥ 500 V
Leakage current at U
0 µA
Signalling contact
No
Standards
IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006
Voltage type
AC/DC

Dimensions And Weights

Width
17.8 mm
Width (inches)
0.701 inch
Height
90 mm
Height (inches)
3.543 inch
Depth
69 mm
Depth (inches)
2.717 inch
Net weight
75 g

Csa Protection Data

Gas group C
IIB
Gas group D
IIA
Gas groups A, B
IIC
Input current, max. I
350 mA
Internal capacity, max. C
0 nF
Internal inductance, max. L
0 µH

Connection Data

Type of connection
Screw connection
Stripping length, rated connection
7 mm
Tightening torque, min.
0.5 Nm
Tightening torque, max.
0.8 Nm
Clamping range, min.
0.5 mm²
Clamping range, max.
4 mm²
Wire cross-section, solid, min.
0.5 mm²
Wire cross-section, solid, max.
4 mm²
Wire connection cross section, finely stranded, max.
2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
0.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
2.5 mm²
Connection cross-section, stranded, min.
0.5 mm²
Connection cross-section, stranded, max.
2.5 mm²
Blade size
0.6 x 3.5 mm

Tender Specification Sheets

Long specification
Base unit for floating-ground powered paired cables and 24 V power supplies. With the installation of the base element a contact is established between mounting rail and the integrated sparkover gap. Through this sparkover gap, a high impedance connection between the ground of the protective switch in the protective plug and the earth potential is made. Suitable for ATEX applications. Mechanical coding of the base element to the protected plug according to switching type and rated voltage. The base unit is coded itself by the first insertion of a protected plug. Optical identification of the protected plug based on the type of protected switching and the voltage level. Possible to mark all terminals
Short specification
Base element to receive a protected plug for an floating-ground powered paired cable and 24 V power supply with indirect earthing. Suitable for ATEX applications.

Classifications

ETIM 6.0
EC000472
ETIM 7.0
EC000472
EClass 9.0
27-13-08-03
EClass 9.1
27-13-08-07
EClass 10.0
27-13-08-03
UNSPSC
30-21-19-21

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Temperatures

Humidity
5...96 %
Operating temperature, max.
70 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
80 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...70 °C
Storage temperature
-40 °C...80 °C

Ratings Iecex/Atex/Cul

ATEX certificate
ATEX Certificate
IEC Ex certificate
IECEX Zertifikat
Certificate No. (ATEX)
KEMA10ATEX0148X
CUL certificate
cUL Certificate