Weidmuller

1334480000

1 / 1
thumbnail

Description

Z-series, Fuse terminal, Rated cross-section: 2.5 mm², Tension-clamp connection
Part Number
1334480000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Approvals

Approvals
EAC
ROHS
Conform

Dimensions And Weights

Width
7.9 mm
Width (inches)
0.311 inch
Height
79.5 mm
Height (inches)
3.13 inch
Depth
73 mm
Depth (inches)
2.874 inch
Depth including DIN rail
74 mm
Net weight
19.63 g

Fuse Terminals

Cartridge fuse
G-Si. 5 x 20
Power loss for overload and short-circuit protection for a composite arrangement
1.6 W at 6.3 A @ 41°C
Power loss for overload and short-circuit protection for an individual arrangement
2.5 W at 2.5 A @ 27°C
Power loss for short-circuit protection only for a composite arrangement
2.5 W at 6.3 A @ 55°C
Power loss for short-circuit protection only for an individual arrangement
4.0 W at 6.3 A @ 52°C

Additional Technical Data

Type of mounting
Snap-on

Material Data

Material
Wemid
Colour
blue
UL 94 flammability rating
V-0

Safety Note

Safety notice
Safety Information

Classifications

ETIM 6.0
EC000899
ETIM 7.0
EC000899
EClass 9.0
27-14-11-16
EClass 9.1
27-14-11-16
EClass 10.0
27-14-11-16

System Specifications

Version
Tension-clamp connection, Fuse cartridge, with LED, for plug-in cross-connector, One end without connector
End cover plate required
Yes
Number of potentials
1
Number of levels
1
Number of clamping points per level
2
Number of potentials per tier
1
Levels cross-connected internally
No
PE connection
No
Rail
TS 35
N-function
Yes
PE function
No
PEN function
No

Temperatures

Storage temperature, max.
40 °C
Storage temperature, min.
10 °C
Storage temperature
10 °C...40 °C
Continuous operating temp., min.
-50 °C
Continuous operating temp., max.
120 °C

Rating Data

Rated cross-section
2.5 mm²
Rated voltage
28 V
Rated voltage to adjoining terminal
500 V
Rated current
6.3 A
Volume resistance according to IEC 60947-7-x
1.33 mΩ
Power loss in accordance with IEC 60947-7-x
0.77 W

Conductors For Clamping (Rated Connection)

Number of connections
2
Type of connection
Tension-clamp connection