Weidmuller

2545120000

1 / 7
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail

Description

IT TIMER, Multifunction timing relay, with separate control input, Number of contacts: 1, CO contact, AgNi, Continuous current: 5 A, Screw connection
Part Number
2545120000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

Version
with separate control input
Rail
TS 35
Test button
No
Mechanical switch position indicator
No
Resistance to vibration EN 61812-1
10 Hz...60 Hz: 0.15 mm, 60 Hz...150 Hz: 2 g

Approvals

Approvals
EAC
ROHS
Conform

Dimensions And Weights

Width
17.5 mm
Width (inches)
0.689 inch
Height
98 mm
Height (inches)
3.858 inch
Depth
57.9 mm
Depth (inches)
2.28 inch
Net weight
49.6 g

Connection Data

Wire connection method
Screw connection
Stripping length, rated connection
7 mm
Tightening torque, max.
0.5 Nm
Clamping range, rated connection
2.5 mm²
Clamping range, min.
0.25 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 23
Wire connection cross section AWG, max.
AWG 14
Wire cross-section, solid, min.
0.25 mm²
Wire cross-section, solid, max.
2.5 mm²
Wire connection cross-section, finely stranded, min.
0.25 mm²
Wire connection cross section, finely stranded, max.
2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.25 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
0.25 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
2.5 mm²
Blade size
size PH1

Contact Data

Contact type
1 CO contact (AgNi)
Mechanical service life
1 x 106 switching cycles

Input

Rated control voltage
24...48 V DC - 15 % / + 10 % / 24...240 V AC - 15 % / + 10 %
Power rating
8 VA @ 230 V AC, 0.4 W at 24 V DC
Status indicator
LED green (U/t): flashes when time runs, lights permanently with supply voltage applied, LED yellow (R): relay closed
Repeat accuracy
< 0.5 % or ±5 ms
Setting tolerance
5 %
Basic accuracy
< 1.5 % (of scale-end value)
Min. pulse duration
50 ms
Time ranges
0.05 s - 1 s, 0.5 s - 10 s, 3 s - 60 s, 0.5 min - 10 min, 3 min - 1 h, 0.5 h - 10 h
Max. reset time after voltage interruption
100 ms

Classifications

ETIM 6.0
EC001439
ETIM 7.0
EC001439
EClass 9.0
27-37-16-05
EClass 9.1
27-37-16-05
EClass 10.0
27-37-16-05

Output

Rated switching voltage
250 V AC
Max. switching voltage, AC
250 V
Max. switching voltage, DC
30 V
Continuous current
5 A
AC switching capacity (resistive), max.
1250 VA
DC switching capacity (resistive), max.
90 W

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Rated voltage
300 V
Surge voltage category
II
Pollution severity
2
Protection degree
IP20
Dielectric strength, Input/Output
1.6 kV
Creepage and clearance distance input – output
≥ 1.5 mm
Impulse withstand voltage
2.5 kV

Temperatures

Humidity
25 - 75%, no condensation
Operating temperature, max.
50 °C
Operating temperature, min.
-25 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-40 °C
Operating temperature
-25 °C...50 °C
Storage temperature
-40 °C...70 °C