Weidmuller

2591680000

1 / 2
thumbnail
thumbnail

Description

Surge voltage arrester, Low voltage, Surge protection, with remote contact, Single-phase, UP(L/N-PE) ≤ 1.25 kV
Part Number
2591680000
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
2 pcs.
In-Stock
Updated at: 30-04-2024
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

General Data

Altitude
≤ 4000 m
Colour
orange, black
Design
Installation housing; 2TE, Insta IP 20
Optical function display
green = OK; red = arrester is defective - replace
Protection degree
IP20 in installed state
Rail
TS 35
Segment
Power distribution
UL 94 flammability rating
V-0
Version
Surge protection, with remote contact

Approvals

Approvals
CE, cURus, EAC, VDE
ROHS
Conform
UL File Number Search
E354261

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
III

Rated Data Iec / En

Discharge current I
20 kA
Energy coordination (≤10 m)
Type II, Type III
Follow-on current extinguishing capability I
Follow current need not be taken into account
Frequency range, max.
60 Hz
Frequency range, min.
50 Hz
Fuse
250 gG @50 kA Isccr, 315 gG @25 kA Isccr
Leakage current at U
0.4 mA
Low voltage network
Single-phase
Max. continuous voltage, Uc (AC)
150 V
Number of poles
2
Protection level U
≤ 1.25 kV
Rated voltage (AC)
120 V
Requirements category acc. to IEC 61643-11
Type II
Requirements class, acc. to EN 61643-11
T2
Response time
≤ 25 ns
SPD type
T2
Short-circuit current rating I
50 kA
Signalling contact
250 V 1A 1CO
Standards
IEC61643-11, EN61643-11
Temporary surge voltage (over-voltage) - TOV
229 V
Voltage type
AC

Dimensions And Weights

Width
36 mm
Width (inches)
1.417 inch
Height
95 mm
Height (inches)
3.74 inch
Depth
68 mm
Depth (inches)
2.677 inch
Depth including DIN rail
76 mm
Net weight
270 g

Connection Data

Wire connection method
Screw connection
Type of connection
Screw connection
Stripping length, rated connection
15 mm
Tightening torque, min.
2 Nm
Tightening torque, max.
4.5 Nm
Clamping range, rated connection
16 mm²
Clamping range, min.
4 mm²
Clamping range, max.
35 mm²
Wire cross-section, solid, min.
2.5 mm²
Wire cross-section, solid, max.
35 mm²
Wire connection cross-section, finely stranded, min.
4 mm²
Wire connection cross section, finely stranded, max.
35 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
35 mm²
Connection cross-section, stranded, min.
2.5 mm²
Connection cross-section, stranded, max.
35 mm²

Rated Data Ul

Voltage type
AC
Certificate No. (cURus)
E354261
Rated Voltage U
120 V
VPR (L/N-PE)
1,200 V
SCCR
200 kA
I
20 kA
Category
SPD TYPE 1CA

Classifications

ETIM 6.0
EC000941
ETIM 7.0
EC000941
EClass 9.0
27-13-08-05
EClass 9.1
27-13-08-05
EClass 10.0
27-13-08-05
UNSPSC
30-21-19-21

Connection Data, Remote Alert

Connection type
PUSH IN
Stripping length
8 mm
Cross-section for connected wire, solid core, min.
0.14 mm²
Cross-section for connected wire, solid core, max.
1.5 mm²

Temperatures

Humidity
5 - 95% rel. humidity
Operating temperature, max.
85 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...85 °C
Storage temperature
-40 °C...85 °C