Weidmuller

2618370000

1 / 4
thumbnail
thumbnail
thumbnail
thumbnail

Description

TERMSERIES, solid-state relais, 1 NO contact (Triac (zero-cross switch)), Rated control voltage: 60 V UC ±10 % , Rated switching voltage: 24...240 V AC, Continuous current: 1 A, PUSH IN with actuator
Part Number
2618370000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

Rail
TS 35
Colour
black
UL 94 flammability rating
V-0

Probability Of Failure

MTTF
815 Years

Load Side

Rated switching voltage
24...240 V AC
Continuous current
1 A
Rated switching current
1 A
Inrush current
15 A / 10 ms
Switch-on delay
< 11 ms
Switch-off delay
< 11 ms
Voltage drop at max. load
≤ 1.6 V
Leakage current
< 1.5 mA
Min. switching current
20 mA
Short-circuit-proof
No
Protective circuit, load side
Rectifier
Output voltage frequency range
50 / 60 Hz
Max. switching frequency (AC control voltage)
3 Hz
Max. switching frequency (DC control voltage)
3 Hz

Approvals

Approvals
CULUS, EAC
UL File Number Search
E141197

Dimensions And Weights

Width
6.4 mm
Width (inches)
0.252 inch
Height
89.4 mm
Height (inches)
3.52 inch
Depth
87.8 mm
Depth (inches)
3.457 inch
Net weight
0 g

Connection Data

Wire connection method
PUSH IN with actuator
Stripping length, rated connection
8 mm
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.14 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 14
Wire cross-section, solid, min.
0.14 mm²
Wire cross-section, solid, max.
2.5 mm²
Wire connection cross-section, finely stranded, min.
0.14 mm²
Wire connection cross section, finely stranded, max.
2.5 mm²
Wire cross-section, finely stranded, min. (AWG)
AWG 26
Wire cross-section, finely stranded, max. (AWG)
AWG 14
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.15 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
1.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
0.15 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
1.5 mm²
Twin wire-end ferrules, min.
0.5 mm²
Twin wire-end ferrules, max.
1 mm²
Blade size
0.4 x 2.0 mm

Contact Data

Contact type
1 NO contact (Triac (zero-cross switch))

Control Side

Rated control voltage
60 V UC ±10 %
Nominal control current
4.8 mA AC (±10 %), 2.5 mA DC (±10 %)
Power rating
< 300 mW
Cut-in / dropout voltage
35 V / 20 V AC35 V / 26 V DC
Status indicator
Green LED
Protective circuit
Rectifier
Coil voltage of the replacement relay deviating from the rated control voltage
Yes
Coil voltage of the replacement relay
60 V DC

Classifications

ETIM 6.0
EC001504
ETIM 7.0
EC001504
EClass 9.0
27-37-16-04
EClass 9.1
27-37-16-04
EClass 10.0
27-37-16-04

Insulation Coordination

Rated voltage
300 V
Pollution severity
2
Surge voltage category
III
Clearance and creepage distances for control side - load side
≥ 5.5 mm
Dielectric strength for control side - load side
2.5 kVeff
Dielectric strength to mounting rail
4 kVeff / 1 Min.
Impulse withstand voltage
6 kV (1.2/50 µs)
Protection degree
IP20

Temperatures

Humidity
5-95% relative humidity, Tu = 40°C, without condensation
Operating temperature, max.
60 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-40 °C
Operating temperature
-20 °C...60 °C
Storage temperature
-40 °C...70 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E141197

Further Details Of Approvals / Standards

Standards
DIN EN 50178
Certificate no. (cULus)
E141197