Weidmuller
7940010232
1 / 2
Description
Process monitoring, 0...200 µS (resolution 0.1 µS)0...1000 / 5000 µS (resolution 1 µs)0...20 mS (0.01 mS resolution)0...200 °C (0.1 °C resolution)- Part Number
- 7940010232
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
General Data
- Accuracy
- ± 0.05 % of final value
- Input/Output
- Voltage/current output
- Linearity
- ± 0.05 % of signal range
- Long-term drift
- 0.1 % / 10.000 h
- Power consumption
- 6 W @ 24 V DC
- Rail
- TS 35, TS 32
- Repeat accuracy
- ± 0.05 % of signal range
- Sampling rate
- 5x pro s
- Step response time
- 320 ms (10...90 %),adjustable (250 ms...32 s)
- Temperature coefficient
- ≤ 0.02 % / °C
- Voltage supply
- 12...50 V DC
Approvals
- Approvals
- CE, CULUS
- ROHS
- Conform
- UL File Number Search
- E256486
Display
- Type
- 4-character display
- Display range
- -999...9999
- Display value
- µS, mS, µS/cm, mS/cm or °C
- Resolution (display)
- Refer to input signal
Dimensions And Weights
- Width
- 46 mm
- Width (inches)
- 1.811 inch
- Height
- 97 mm
- Height (inches)
- 3.819 inch
- Depth
- 120 mm
- Depth (inches)
- 4.724 inch
- Weight
- 500 g
- Net weight
- 500 g
Connection Data
- Type of connection
- Screw connection
- Clamping range, rated connection
- 1.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, max.
- 2.5 mm²
Alarm Output
- Type
- Alarm output with 2 NO contacts and suppressor circuit
- Switching current
- 1 A @ 240 V AC / 30 V DC
Input
- Type
- Conductivitiy, PT100 RTD
- Sensor supply
- ≤ 6 Vss @ 400 Hz
- Input signal
- 0...200 µS (resolution 0.1 µS)0...1000 / 5000 µS (resolution 1 µs)0...20 mS (0.01 mS resolution)0...200 °C (0.1 °C resolution)
- Cable-length compensation
- < 2 % (up to 30 Ω)
Output (Analogue)
- Load resistance current
- ≤ 900 Ω
- Load resistance voltage
- ≥ 1 kΩ
- Output current
- 0...22 mA
- Output voltage
- 0...11 V
- Transmit function
- direct or inverted
- Type (analogue output)
- Voltage and current output (configurable)
Classifications
- ETIM 6.0
- EC000677
- ETIM 7.0
- EC000677
- EClass 9.0
- 27-14-31-10
- EClass 9.1
- 27-21-03-01
- EClass 10.0
- 27-14-31-10
- UNSPSC
- 30-21-18-01
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Insulation Coordination
- EMC standards
- DIN EN 61326
- Impulse withstand voltage
- 4 kV (1.2/50 µs)
- Insulation voltage
- 2 kV input / output / power supply
- Rated voltage
- 300 Veff
Temperatures
- Humidity
- 0...90 % (no condensation)
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- 0 °C
- Storage temperature, max.
- 70 °C
- Storage temperature, min.
- -25 °C
- Operating temperature
- 0 °C...60 °C
- Storage temperature
- -25 °C...70 °C
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E256486
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther