General Data

Accuracy
± 0.05 % of final value
Input/Output
Voltage/current output
Linearity
± 0.05 % of signal range
Long-term drift
0.1 % / 10.000 h
Power consumption
6 W @ 24 V DC
Rail
TS 35, TS 32
Repeat accuracy
± 0.05 % of signal range
Sampling rate
5x pro s
Step response time
320 ms (10...90 %),adjustable (250 ms...32 s)
Temperature coefficient
≤ 0.02 % / °C
Voltage supply
12...50 V DC

Approvals

Approvals
CE, CULUS
ROHS
Conform
UL File Number Search
E256486

Display

Type
4-character display
Display range
-999...9999
Display value
µS, mS, µS/cm, mS/cm or °C
Resolution (display)
Refer to input signal

Dimensions And Weights

Width
46 mm
Width (inches)
1.811 inch
Height
97 mm
Height (inches)
3.819 inch
Depth
120 mm
Depth (inches)
4.724 inch
Weight
500 g
Net weight
500 g

Connection Data

Type of connection
Screw connection
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Alarm Output

Type
Alarm output with 2 NO contacts and suppressor circuit
Switching current
1 A @ 240 V AC / 30 V DC

Input

Type
Conductivitiy, PT100 RTD
Sensor supply
≤ 6 Vss @ 400 Hz
Input signal
0...200 µS (resolution 0.1 µS)0...1000 / 5000 µS (resolution 1 µs)0...20 mS (0.01 mS resolution)0...200 °C (0.1 °C resolution)
Cable-length compensation
< 2 % (up to 30 Ω)

Output (Analogue)

Load resistance current
≤ 900 Ω
Load resistance voltage
≥ 1 kΩ
Output current
0...22 mA
Output voltage
0...11 V
Transmit function
direct or inverted
Type (analogue output)
Voltage and current output (configurable)

Classifications

ETIM 6.0
EC000677
ETIM 7.0
EC000677
EClass 9.0
27-14-31-10
EClass 9.1
27-21-03-01
EClass 10.0
27-14-31-10
UNSPSC
30-21-18-01

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

EMC standards
DIN EN 61326
Impulse withstand voltage
4 kV (1.2/50 µs)
Insulation voltage
2 kV input / output / power supply
Rated voltage
300 Veff

Temperatures

Humidity
0...90 % (no condensation)
Operating temperature, max.
60 °C
Operating temperature, min.
0 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-25 °C
Operating temperature
0 °C...60 °C
Storage temperature
-25 °C...70 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E256486