Weidmuller

8432250000

1 / 3
thumbnail
thumbnail
thumbnail

Description

RTD transformer, Tension-clamp connection
Part Number
8432250000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

Accuracy
100K ≤ MB < 600K: 0,.1 %; MB ≥ 600K: 0.2 %; of the MB
Configuration
DIP switch, Potentiometer, and PT100-Simulator
Current consumption
< 38 mA @ IOUT = 20 mA
Current-carrying capacity of cross-connect.
≤ 2 A
Galvanic isolation
Without isolation
Input/Output
PT100/ 0...10 V
Linearity
Yes
Rail
TS 35
Temperature coefficient
Measuring range ≥ 200 K: ≤ 200 ppm/K (typ. 80 ppm/K)100 K < = measuring range < 200 K: < 225 ppm/K (typ. 90 ppm/K)
Voltage supply
24 V DC ± 20 %

Approvals

Approvals
CE, CSA, CULUS
ROHS
Conform
UL File Number Search
E141197

Dimensions And Weights

Length
92.4 mm
Length (inches)
3.638 inch
Width
12.5 mm
Width (inches)
0.492 inch
Depth
112.4 mm
Depth (inches)
4.425 inch
Net weight
127 g

Connection Data

Type of connection
Tension-clamp connection
Stripping length, rated connection
7 mm
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Tender Specification Sheets

Long specification
PT100 temperature measuring transformer, configured with DIP switches, 4-wire connection technologyRTD measurement isolating transformer in 12.5 mm width with external power supply,for transmitting PT100 4-wire signals.Input temperature range -200...+800 °C.Analogue DC signals 0...10 V are available on the output side.Zero/span compensation with potentiometer.  Add-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 12.5/ 112.4 mmTension-clamp connection / Nominal cross-section 1.5 mm2Protection degree: IP 20  Input                          PT100, 4-wireOutput                                              0...10 VLoad resistance > 1 kOhm Transmission error             < 0,5 % v. E.                                         typ. 200 ppm / °CAuxiliary power                                     24 VDC +/- 20 %Ambient temperature range 0°C...+55 °CIsolation                                no electrical isolationApprovals cULus, CSAType                                                             WTZ4 PT100/4 C 0-10V
Short specification
PT100 temperature measuring transformer, configured with DIP switches, 4-wire connection technologyRTD measurement isolating transformer in 12.5 mm width with external power supply,for transmitting PT100 4-wire signals.Input temperature range -200...+800 °C.Analogue DC signals 0...10 V are available on the output side.Zero/span compensation with potentiometer.

Input

Number of inputs
1
Sensor
PT100 / 2-/3-/4-wire
Sensor supply
1.45 mA
Temperature input range
Adjustable from -200...+800°C

Classifications

ETIM 6.0
EC002919
ETIM 7.0
EC002919
EClass 9.0
27-21-01-29
EClass 9.1
27-21-01-29
EClass 10.0
27-21-01-29
UNSPSC
30-21-18-01

Output

Number of outputs
1
Output voltage, note
0...10 V
Load impedance voltage
≥ 1 kΩ

Product Information

Product information
This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

EMC standards
EN 55011, EN 61000-6
Galvanic isolation
Without isolation

Temperatures

Operating temperature, max.
55 °C
Operating temperature, min.
0 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-20 °C
Operating temperature
0 °C...55 °C
Storage temperature
-20 °C...85 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E141197