Weidmuller

8560710000

1 / 4
thumbnail
thumbnail
thumbnail
thumbnail

Description

RTD isolating transformer, Tension-clamp connection
Part Number
8560710000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

Accuracy
< 0.3 % of measured value
Configuration
DIP switch, Potentiometer
Current-carrying capacity of cross-connect.
≤ 2 A
Galvanic isolation
3-way isolator
Input/Output
configurable
Linearity
Yes
Power consumption
830...880...980 mW at IOUT = 20 mA
Rail
TS 35
Step response time
fast/slow: 2-/3-/4-conductor: 1.2 s/2.2 s; potentiometer: 0.5 s/1.1 s
Temperature coefficient
Measuring range ≥ 200 K: ≤ 200 ppm/K100 K <= measuring range < 200 K: <= 250 ppm/K40 K <= measuring range < 100 K: ≤ 400 ppm/K
Voltage supply
24 V DC ± 20 %

Probability Of Failure

MTTF
270 Years

Approvals

Approvals
CE, CULUS, EAC, GERMLLOYD
ROHS
Conform
UL File Number Search
E141197

Dimensions And Weights

Length
92.4 mm
Length (inches)
3.638 inch
Width
17.5 mm
Width (inches)
0.689 inch
Depth
112.4 mm
Depth (inches)
4.425 inch
Weight
100 g
Net weight
140 g

Connection Data

Type of connection
Tension-clamp connection
Stripping length, rated connection
7 mm
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Tender Specification Sheets

Long specification
RTD measurement isolating transformer; configured with DIP switchesRTD measurement isolating transformer in 17.5 mm width with external power supply,for transmitting and isolating PT100 and Ni100 2-/3-/-4-wire signals, resistors and potentiometer signals.Analogue DC signals 0(4) to 20 mA / 0 to 10 V are available on the output side.Zero/span compensation with potentiometer. Add-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 17.5/ 112.4 mmTension-clamp connection / Nominal cross-section 1.5 mm2Protection degree: IP 20   Input                         PT100, Ni100 2-/3-/4-wire                                      Resistance 0...450 Ohm/ Potentiometer100 Ohm...100 kOhm                                                                          Output                                             0/4...20 mA                                       0...10 V Load resistance             < 600 Ohm/ Strom/> 1 kOhm/ voltageTransmission error             < 0,8 % v. E.  ( RTD)                                       typ. 200 ppm / °CAuxiliary power                                     24 VDC +/- 25 %Power loss approx. 0.9 WAmbient temperature range 0°C...+55 °CIsolation                                 EN 50178, 3-way isolation up to 4 kV AC/DC of all circuits against each otherTest voltage                              4 kV input against output against auxiliary powerRated voltage                                          300 V AC/DC at overvoltage category III and pollution degree 2Approvals cULus, cULusEX, GLType                                                             WAZ5 PRO RTD
Short specification
RTD measurement isolating transformer; configured with DIP switchesRTD measurement isolating transformer in 17.5 mm width with external power supply,for transmitting and isolating PT100 and Ni100 2-/3-/-4-wire resistor signals and potentiometer signals. Analogue DC signals 0(4) to 20 mA / 0 to 10 V are available on the output side. Zero/span compensation with potentiometer.

Input

Number of inputs
1
Sensor
PT100/2-/3-/4-wire, Ni100/2-/3-/4-wire, potentiometer: min. 0–100 Ω, max. 0–100 kΩ, resistance: 0–450 Ω
Line resistance in measuring circuit
50 Ω for 3- and 4-conductor
Temperature input range
Configurable, PT100: -200°C…850 °C, NI100: -60°C…+250 °C

Classifications

ETIM 6.0
EC002919
ETIM 7.0
EC002919
EClass 9.0
27-21-01-29
EClass 9.1
27-21-01-29
EClass 10.0
27-21-01-29
UNSPSC
30-21-18-01

Output

Number of outputs
1
Output voltage, note
0...10 V
Output current
0...20 mA, 4...20 mA
Wire break detection
LED flashing (output value: > 20 mA, >10 V)
Fine adjustment
≥ ± 5 %, Version 1 and later: ≥ 12.5 % / potentiometer: 12.5%...25%
Load impedance voltage
≥ 1 kΩ
Load impedance current
≤ 600 Ω
Offset voltage
max. 0.05 V
Offset current
max. 100 µA
Status indicator
Module active: LED on/ wire breakage: LED flashing/Error: LED off

Product Information

Product information
This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Clearance & creepage distances
≥ 3 mm
EMC standards
EN 55011, EN 61000-6
Galvanic isolation
3-way isolator
Impulse withstand voltage
4 kV
Insulation voltage
2 kVeff / 5 s
Insulation voltage input or output/rail
4 kVeff / 1 min.
Insulation voltage input or output/supply
2 kVeff / 5 s
Pollution severity
2
Rated voltage
300 V
Surge voltage category
III

Temperatures

Operating temperature, max.
55 °C
Operating temperature, min.
0 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-20 °C
Operating temperature
0 °C...55 °C
Storage temperature
-20 °C...85 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E141197