Weidmuller

8948620000

1 / 2
thumbnail
thumbnail

Description

MCZ SERIES, Surge protection for instrumentation and control, 0.5 A
Part Number
8948620000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

Colour
black
Design
Terminal
Height with TS 35
63.5 mm
Protection degree
IP20
Rail
TS 35
Segment
Measurement - Monitoring - Setting
UL 94 flammability rating
V-0
Version
Surge protection for measurement and control

Approvals

Approvals
CE, EAC
ROHS
Conform

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
III

Rated Data Iec / En

Discharge current, max. (8/20 µs)
5 kA
Fuse
0.5 A
Limiting frequency (-3 dB) at load resistance
100 MHz (measured in 100-Ω system)
Max. continuous voltage, Uc (AC)
7 V
Operating current, I
0.3 A
Operating voltage
7 A
Protection level on output side Wire-PE 1kV/µs, typically
15 V
Protection level on output side Wire-PE 8/20 µs, typically
30 V
Protection level on output side Wire-wire 1 kV/µs, typically
15 V
Protection level on output side Wire-wire 8/20 µs, typically
15 V
Rated current I
0.5 A
Rated voltage (AC)
5 V
Rated voltage (DC)
5 V
Rated voltage (DC), max.
10 V
Requirements category acc. to IEC 61643-21
D1, C3, C2, C1
Response time
≤ 100 ps
Voltage type
AC/DC
Volume resistance
2.50 Ω

Dimensions And Weights

Width
6 mm
Width (inches)
0.236 inch
Height
91 mm
Height (inches)
3.583 inch
Depth
63.5 mm
Depth (inches)
2.5 inch
Net weight
27.2 g

Connection Data

Cross-section
1.5 mm²
Wire connection method
Tension-clamp connection
Type of connection
Tension-clamp connection
Stripping length, rated connection
8 mm
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
1.5 mm²
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 16
Wire cross-section, solid, min.
0.5 mm²
Wire cross-section, solid, max.
1.5 mm²
Wire connection cross-section, finely stranded, min.
0.5 mm²
Wire connection cross section, finely stranded, max.
1.5 mm²
Wire cross-section, finely stranded, min. (AWG)
AWG 26
Wire cross-section, finely stranded, max. (AWG)
AWG 16
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
1.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
0.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
1.5 mm²
Blade size
0.6 x 3.5 mm

Classifications

ETIM 6.0
EC000943
ETIM 7.0
EC000943
EClass 9.0
27-13-08-07
EClass 9.1
27-13-08-07
EClass 10.0
27-13-08-07
UNSPSC
30-21-18-01

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Temperatures

Operating temperature, max.
60 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...60 °C
Storage temperature
-40 °C...85 °C