Description
Surge protection for instrumentation and control, 24 V, 300 mA, IEC 61643-21- Part Number
- 8951630000
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 4 pcs.In-StockUpdated at: 30-04-2024
- Estimated Delivery:
- On Request
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Further Details Of Approvals
- GOST certificate
- GOST-Zertifikat
General Data
- Colour
- orange
- Design
- Terminal, miscellaneous
- Optical function display
- green = OK; red = arrester is defective - replace
- Protection degree
- IP20
- Segment
- Measurement - Monitoring - Setting
- UL 94 flammability rating
- V-0
- Version
- with warning function / function indicator
- Protected binary signals
- 2
Probability Of Failure
- Λges
- 43
- MTTF
- 2,665 Years
- PFH in 1*10
- 10.7
- SFF
- 86.02 %
- SIL PAPER
- SIL Paper
- SIL in compliance with IEC 61508
- 2
Approvals
- Approvals
- CE, CSAEX, EAC, FUSAFETY, OEVE, UL
- ROHS
- Conform
- UL File Number Search
- E311081
Insulation Coordination Acc. To En 50178
- Pollution severity
- 2
- Surge voltage category
- III
Rated Data Iec / En
- Discharge current I
- 2.5 kA
- Fuse
- 0.5 A
- Lightning test current, I
- 2.5 kA
- Max. continuous voltage, Uc (DC)
- 28 V
- Number of poles
- 1
- Overload - failure mode
- Modus 2
- Protection level U
- < 200 V
- Protection level on output side Wire-PE 1kV/µs, typically
- 40 V
- Protection level on output side Wire-wire 1 kV/µs, typically
- 80 V
- Protection level on output side Wire-wire 8/20 µs, typically
- 80 V
- Protection level, U
- 40 V
- Pulse-reset capacity
- ≤ 30 ms
- Rated current I
- 300 mA
- Rated voltage (DC)
- 24 V
- Requirements category acc. to IEC 61643-21
- C1, C2, C3, D1
- Signal transmission properties (-3 dB)
- 2.7 MHz
- Signalling contact
- UN 250 V AC 0.1 A 1CO at VSPC R with VSPC control unit
- Standards
- IEC 61643-21
- Surge current-carrying capacity C1
- < 1 kA 8/20 μs
- Surge current-carrying capacity C2
- 5 kA 8/20 μs
- Surge current-carrying capacity C3
- 100 A 10/1000 μs
- Surge current-carrying capacity D1
- 2.5 kA 10/350 μs
- Voltage type
- DC
- Volume resistance
- 4.7 Ω
Dimensions And Weights
- Width
- 17.8 mm
- Width (inches)
- 0.701 inch
- Height
- 98 mm
- Height (inches)
- 3.858 inch
- Depth
- 69 mm
- Depth (inches)
- 2.717 inch
- Net weight
- 45 g
Csa Protection Data
- Gas group C
- IIB
- Gas group D
- IIA
- Gas groups A, B
- IIC
- Input voltage, max. U
- 28 V
- Internal capacity, max. C
- 2 nF
- Internal inductance, max. L
- 0 µH
Connection Data
- Type of connection
- Pluggable in VSPC BASE
Rated Data Ul
- Certificate No. (UL)
- E311081
- UL certificate
- UL 497b Certificate
Tender Specification Sheets
- Long specification
- Surge protection plug for use in connection with the base element VSPC BASE 2SL R for two wires with a common ground and with integrated status display and remote monitoring option. Two-stage protection circuit in the plug consisting of coarse protection, decoupling resistors and fine protection between the signal wires and the signal ground/ground/earth. Mechanical identification of the plug to the base element according to the switching type and rated voltage. Protected plug with coding pin and counter-profile for the base element. Optical identification of the protected plug based on the type of protected switching and the voltage level. It is possible to mark the plug.
- Short specification
- Surge protection plug for base element VSPC BASE 2SL R, with integrated status display and remote monitoring option. Coarse and fine common mode voltage protection for two wires with a common ground. Version: 24 V DC
Classifications
- ETIM 6.0
- EC000943
- ETIM 7.0
- EC000943
- EClass 9.0
- 27-13-08-07
- EClass 9.1
- 27-13-08-07
- EClass 10.0
- 27-13-08-07
- UNSPSC
- 30-21-19-21
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Temperatures
- Humidity
- 5...96 %
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -40 °C
- Storage temperature, max.
- 80 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -40 °C...70 °C
- Storage temperature
- -40 °C...80 °C
Ratings Iecex/Atex/Cul
- CUL certificate
- cUL Certificate
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther