Weidmuller

8953590000

1 / 5
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail

Description

Surge protection for instrumentation and control, 12 V, 350 mA, IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006, HART-compatible
Part Number
8953590000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Further Details Of Approvals

GOST certificate
GOST-Zertifikat

Protection Ex - Data

ATEX - dust labelling
II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling
II 1 G Ex ia IIC T4… T6 Ga
Certificate No. (ATEX)
KEMA10ATEX0148X
IECEx - dust labelling
II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling
II 1 G Ex ia IIC T4… T6 Ga
Input power, max. P
3 W
Input voltage, max. U
14 V
Internal capacity, max. C
< 4 nF
Internal inductance, max. L
0 µH
Temperature class T4/135°C (-40°C ... +85°C) li
350 mA
Temperature class T5/100°C (-40 ° C ... +75°C) li
250 mA
Temperature class T6/85 °C (-40 °C ... +60°C) li
250 mA

General Data

Colour
Light Blue
Design
Terminal, miscellaneous
Optical function display
No
Protection degree
IP20
Segment
Measurement - Monitoring - Setting
UL 94 flammability rating
V-0
Version
without warning function / function indicator
Protected current loops
1

Probability Of Failure

Λges
45
MTTF
2,537 Years
PFH in 1*10
1.95
SFF
95.67 %
SIL PAPER
SIL Paper
SIL in compliance with IEC 61508
3

Approvals

Approvals
CE, CSAEX, EAC, FUSAFETY, IECEXDEK, KEMAATEX
ROHS
Conform

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
III

Rated Data Iec / En

Dielectric strength at FG against PE
≥ 500 V
Discharge current I
2.5 kA
Input voltage, max. U
14 V
Lightning test current, I
2.5 kA
Max. continuous voltage, Uc (DC)
14 V
Number of poles
1
Overload - failure mode
Modus 2
Protection level U
< 800 V
Protection level on output side Wire-PE 1kV/µs, typically
450 V
Protection level on output side Wire-wire 1 kV/µs, typically
25 V
Protection level on output side Wire-wire 8/20 µs, typically
25 V
Protection level, U
25 V
Pulse-reset capacity
≤ 20 ms
Rated current I
350 mA
Rated voltage (DC)
12 V
Requirements category acc. to IEC 61643-21
C1, C2, C3, D1
Signal transmission properties (-3 dB)
1.7 MHz
Signalling contact
No
Standards
IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006, HART-compatible
Surge current-carrying capacity C1
< 1 kA 8/20 μs
Surge current-carrying capacity C2
5 kA 8/20 μs
Surge current-carrying capacity C3
100 A 10/1000 μs
Surge current-carrying capacity D1
1 kA 10/350 μs
Voltage type
DC
Volume resistance
2.20 Ω

Dimensions And Weights

Width
17.8 mm
Width (inches)
0.701 inch
Height
90 mm
Height (inches)
3.543 inch
Depth
69 mm
Depth (inches)
2.717 inch
Net weight
45 g

Csa Protection Data

Gas group C
IIB
Gas group D
IIA
Gas groups A, B
IIC
Input voltage, max. U
14 V
Internal capacity, max. C
4 nF
Internal inductance, max. L
0 µH

Connection Data

Type of connection
Pluggable in VSPC BASE

Tender Specification Sheets

Long specification
Surge protection plug for use in connection with the base element VSPC BASE 1CL FG for one floating-ground driven paired cable.Two-stage protection circuit consisting of coarse protection, decoupling resistors and fine protection between the signal wires and coarse common mode voltage protection to earth suitable for use in intrinsically-safe Ex ia circuits. Mechanical identification of the plug to the base element according to the switching type and rated voltage. Optical identification of the protected plug based on the type of protected switching and the voltage level. Protected plug with coding pin and counter-profile for the base element. It is possible to mark the plug.
Short specification
Surge protection plug for base element VSPC BASE 1CL FG, transverse voltage coarse and fine protection of one floating-ground powered paired cable, suitable for use in intrinsically-safe Ex ia circuits, coarse common mode voltage protection to earth. Version: 12V DC

Classifications

ETIM 6.0
EC000943
ETIM 7.0
EC000943
EClass 9.0
27-13-08-07
EClass 9.1
27-13-08-07
EClass 10.0
27-13-08-07
UNSPSC
30-21-19-21

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Temperatures

Humidity
5...96 %
Operating temperature, max.
70 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
80 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...70 °C
Storage temperature
-40 °C...80 °C

Ratings Iecex/Atex/Cul

ATEX certificate
ATEX Certificate
IEC Ex certificate
IECEX Zertifikat
Certificate No. (ATEX)
KEMA10ATEX0148X
CUL certificate
cUL Certificate