Weidmuller
8965380000
1 / 9
Description
EX signal isolating converter, Ex-input: NAMUR sensor/switch, Safe-output: relay, NC contact, 2-channel- Part Number
- 8965380000
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Probability Of Failure
- MTBF
- 207 Years
- SIL PAPER
- SIL certificate
- SIL in compliance with IEC 61508
- 2
Digital Output
- Switching capacity
- 500 VA / 60 W (safe area), 16 VA / 60 W (zone 2)
- Type
- Relay, 1 NC contact, Switching frequency 20 Hz
- Nominal switching voltage
- ≤ 250 V AC / 30 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
- Continuous current
- ≤ 2 A AC/DC (safe area, Zone 2 area)
- Function
- Output = input, direct or inverse (configurable)
Approvals
- ROHS
- Conform
- UL File Number Search
- E337701
Dimensions And Weights
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
- Height
- 119.2 mm
- Height (inches)
- 4.693 inch
- Depth
- 113.6 mm
- Depth (inches)
- 4.472 inch
- Net weight
- 192 g
Safety-Related Specifications Low Demand Mode
- Average Probability of Failure on Demand (PFD
- 2.04 x 10-4 (Tproof = 1 year), 4.08 x 10-4 (Tproof = 2 years), 1.02 x 10-4 (Tproof = 5 years)
- Safe Failure Fraction (SFF)
- 90 %
Connection Data
- Type of connection
- Screw connection
- Tightening torque, min.
- 0.4 Nm
- Tightening torque, max.
- 0.6 Nm
- Clamping range, rated connection
- 2.5 mm²
- Clamping range, min.
- 0.25 mm²
- Clamping range, max.
- 2.5 mm²
- Wire connection cross section AWG, min.
- AWG 26
- Wire connection cross section AWG, max.
- AWG 12
Rated Data Ul
- UL certificate
- E337701.pdf
Safety-Related Basic Specifications
- Demand mode
- High
- Demand rate
- 1,000 s
- Demand response time
- < 10 ms (relay output)
- Description of the "safe state"
- de-energized (relay output)
- Device type
- B
- Diagnostic test interval
- 10 s
- Hardware fault tolerance (HFT)
- 0
- Mean Time To Repair (MTTR)
- 8 h
- Relay lifetime
- 100000 times
- Safe Failure Fraction (SFF)
- 90 %
- T
- 4 Years
- Total failure rate for dangerous detected failures (λ
- 130 FIT
- Total failure rate for dangerous undetected failures (λ
- 46 FIT
- Total failure rate for safe detected failures (λ
- 0 FIT
- Total failure rate for safe undetected failures (λ
- 289 FIT
- Safety category
- SIL 2
- Probability of outage PFH
- 4.66 x 10-8 h-1
Tender Specification Sheets
- Long specification
- Ex isolating switch amplifiers for Namur sensors, 2 channels 2-channel isolating switch amplifiers in 22.5 mm width with an external power supply, to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe zone. On the output side there is a potential-free relay contact per channel with opening function and a common alarm contact ("a" contact) for status/error messages. The component can be configured using standard FDT/DTM software. Add-on housing for TS35 DIN rail installation Dimensions: L/W/H 119.2/ 22.5/ 113.6screw connection / nominal cross-section 2.5 mm2Protection degree: IP20 Input /channel NAMUR sensor according to EN 60947 8 VDC / 8 mA sensor power supply 0.5 kHz input frequency wire-break detectionOutput Ex/ channel Relay 1 NC contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 5 kHz 32 VDC @ 1 A zone 2Alarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2 Auxiliary power 19...31.2 VDCPower loss approx. 3 WAmbient temperature range -20 °C to +60 °C Secure isolation EN 61010, 4-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2 Approvals cULus, ATEX IECEX, FM ATEX marking II 3 G ExnA nC IIC T4 ATEX characteristic data U0 = 10, 6 V DC I0 = 12 mA DC P0 = 32 W Type ACT20X-HDI-2SDO-2RNC-S
- Short specification
- Ex isolating switch amplifiers for Namur sensors, 2 channels2-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe zone. On the output side there is a potential-free relay contact per channel with opening functionand a common alarm contact ("a" contact) for status/error messages.The component can be configured using standard FDT/DTM software.
Alarm Output
- Alarm function
- Line interruption at the input, Short circuit at input, No supply voltage, Device error
- Type
- Relay, 1 NC (voltage-free)
- Nominal switching voltage
- ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
- Continuous current
- ≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0,5 A AC / 1 A DC (zone 2)
- Power rating
- ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Classifications
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- EClass 9.0
- 27-21-01-20
- EClass 9.1
- 27-21-01-20
- EClass 10.0
- 27-21-01-20
- UNSPSC
- 30-21-18-01
Product Information
- Product information
- Weidmüller provides an extended guarantee period of 36 months for this device.The ACT20X-HDI-SDO/ 2HDI-2SNO RNO/RNC isolating switch amplifiers are specially designed for recording NAMUR sensor signals and digital switching signals which originate from Ex zone 0.Switching relays, optionally available with NO or NC contacts, transfer output signals to the safe zone. Integrated alarm contacts issue an alert in the event of a malfunction; this makes troubleshooting easier and increases system availability.The rail mounted disconnect-switch amplifiers are optionally available in one- or two-channel versions. With 11 mm width per channel, the devices need little space in the electrical cabinet.
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Data For Ex Applications (Atex)
- Voltage U
- 10.6 V DC
- Current I
- 12 mA DC
- Power P
- 32 mW
- Marking
- II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Installation location
- Device installed in safe area, zone 2
Insulation Coordination
- EMC standards
- DIN EN 61326, NE 21
- Insulation voltage
- 2.6 kV (input / output)
- Rated voltage
- 300 V
Input Ex
- Input frequency
- < 20 Hz
- Input resistance
- 1 kΩ
- Output signal in case of wire break
- < 0.1 mA, > 6.5 mA (in case of wire break)
- Pulse duration
- > 0.1 ms
- Resistance
- RP = 750 Ω / RS = 15kΩ
- Sensor
- NAMUR sensor, according to EN60947, switch with or without RS, RP
- Sensor supply
- 8 V DC / 8 mA
- Trigger level high
- > 2.1 mA
- Trigger level low
- < 1.2 mA
- Type
- intrinsically safe circuit
Temperatures
- Humidity
- 0...95 % (no condensation)
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- -20 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
- Operating temperature
- -20 °C...60 °C
- Storage temperature
- -20 °C...85 °C
Ratings Iecex/Atex/Cul
- ATEX certificate
- 09ATEX0168X.pdf
- IEC Ex certificate
- IECEx certification
- Certificate No. (ATEX)
- KEMA09ATEX0168X
- Certificate No. (IECEX)
- IECEXKEM09.0072X
- Certificate no. (cULus)
- E337701
General Specifications
- Configuration
- With FDT/DTM software
- Voltage supply
- 19.2…31.2 V DC
- Type of connection
- Screw connection
- NAMUR supply
- 8 V DC / 8 mA
- Power consumption
- ≤1.9 W
- Protection degree
- IP20
- Humidity
- 0...95 % (no condensation)
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther