Weidmuller
8965500000
1 / 5
Description
ACT20M, Supply module, Screw connection- Part Number
- 8965500000
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
General Data
- Degree of efficiency
- 0,976
- Power consumption
- < 2 W
- Rail
- TS 35, CH20M Bus
- Voltage supply
- 21.6...26.4 V DC
Approvals
- Approvals
- CULUS, DEKRAATEX, DETNORVER, EAC, FMEX, IECEXDEK
- ROHS
- Conform
- UL File Number Search
- E337701
Dimensions And Weights
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
- Height
- 117.2 mm
- Height (inches)
- 4.614 inch
- Depth
- 113.6 mm
- Depth (inches)
- 4.472 inch
- Weight
- 140 g
- Net weight
- 173 g
Connection Data
- Type of connection
- Screw connection
- Tightening torque, min.
- 0.4 Nm
- Tightening torque, max.
- 0.6 Nm
- Clamping range, rated connection
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, max.
- 2.5 mm²
- Wire connection cross section AWG, min.
- AWG 30
- Wire connection cross section AWG, max.
- AWG 14
Rated Data Ul
- UL certificate
- E337701.pdf
Input
- Number of inputs
- 2
- Input voltage
- 21.6…26.4 V DC
- Supply voltage (input)
- 21.6...26.4 V DC
- Input current
- max. 4 A
- Backup power supply
- 21.6...26.4 V DC
- Trigger level for the power supply
- Fault < 21 V DC
Classifications
- ETIM 6.0
- EC001600
- ETIM 7.0
- EC001600
- EClass 9.0
- 27-24-26-10
- EClass 9.1
- 27-24-26-10
- EClass 10.0
- 27-24-26-10
- UNSPSC
- 30-21-18-01
Output
- Number of outputs
- 1
- Output voltage, note
- Input voltage -0.5 V DC / 4 A
- Output current
- max. 4 A, (Supply of e.g. 110 devices of ACT20M-CI-2CO-S on one CH20M BUS)
- Output power
- 96 W
- Supply voltage (output)
- 24 V DC
Product Information
- Product information
- The power-feed unit ACT20-FEED-IN-PRO-S distributes the supply voltage for the ACT20 range of devices to the Weidmüller CH20M DIN rail bus. The device also has a connection for a backup power supply. Installation is basically on the Weidmüller CH20M DIN rail bus. Properties The power-feed unit ACT20-FEED-IN-PRO-S detects errors on each of the devices mounted on the Weidmüller CH20M DIN rail and sends a collective message to an external controller via the internal status relay. Two power supplies for the primary and secondary supply (backup) can be optionally connected. A redundant power supply can be set up using two power-feed units and two separate power supplies. The status relay is activated when the following conditions are met: ◊ The supply voltage is on the connection terminals 51 and 52 ◊ The backup supply voltage is on the terminals 53 and 54. If the backup power supply is not required, the supplied jumper needs to be inserted between terminals 52 and 53. ◊ The devices mounted on the Weidmüller DIN rail do not report any errors The device can be used in safe (non-explosive risk) areas or in Zone 2 / Division 2. The operating status of the power supply and the backup power supply is indicated with two green LEDs. A malfunction is indicated with a red LED.
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Insulation Coordination
- EMC standards
- IEC 61326-1, NE 21
Temperatures
- Humidity
- 95 %, no condensation
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
- Ambient temperature
- -20...+60 °C
- Storage temperature
- -20 °C...85 °C
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E337701
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther