Need more information?

Call us at:+48 17 778 34 19

ABB 1SBL136001R2110AF09Z-30-10-21 24-60V50/60HZ 20-60VDC Contactor

1 / 2
1SBL136001R2110 ABB, Electronics
Reference Image - Not actual item!
1SBL136001R2110 ABB, Electronics
1SBL136001R2110 ABB, Electronics
1SBL136001R2110 ABB, Electronics

Offer Description

The AF09Z-30-10-21 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.AF09Z-30-10-21 24-60V50/60HZ 20-60VDC Contactor ABB 1SBL136001R2110

Product Description

The AF09Z-30-10-21 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

Product Details

Brand
ABB
Country of Origin
FR
Part Number
1SBL136001R2110
Tariff Code
85364900
EAN
3471523113213
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, AC switching
Class Code : EC000066
Version : 7
$120.43
excl. tax
Free Shipping!

Offer details

Best offer from:
Trusted Automa.Net Supplier
Availability:
3 pcs.
In-Stock
Updated at: 18-07-2025
Warranty:
12 months
Estimated Delivery:
25-30 July to United States
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
The Seller is responsible for shipping the product and invoicing

Are you a Supplier?

Join 650 suppliers, sell to 3500+ verified buyers.

Sign up now

Policies and Information

Shipping Information

Return & Refund Policies

Secure Payment Process

Warranty Policies

Dimensions

Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.31 kg

Technical

Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 VMain Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 HzControl Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 Aacc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 A(690 V) 60 °C 25 A(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 9 A(440 V) 60 °C 9 A(500 V) 60 °C 9.5 A(690 V) 60 °C 7 A(380 / 400 V) 60 °C 9 A(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 9 A(440 V) 60 °C 9 A(500 V) 60 °C 9.5 A(690 V) 60 °C 7 A(380 / 400 V) 60 °C 9 A(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Power AC-3 (Pe)
(400 V) 4 kW(415 V) 4 kW(440 V) 4 kW(500 V) 5.5 kW(690 V) 5.5 kW(380 / 400 V) 4 kW(220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe)
(415 V) 4 kW(440 V) 4 kW(500 V) 5.5 kW(690 V) 5.5 kW(380 / 400 V) 4 kW(220 / 230 / 240 V) 2.2 kW
Rated Operational Current AC-15 (Ie)
(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 Afor 0.1 s 140 Afor 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour(AC-15) 1200 cycles per hour(AC-2 / AC-4) 300 cycles per hour(AC-3) 1200 cycles per hour(DC-13) 900 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 10 A(110 V) 1-Pole, 60 °C 10 A(110 V) 1-Pole, 70 °C 10 A(110 V) 2 Poles in Series, 40 °C 25 A(110 V) 2 Poles in Series, 60 °C 25 A(110 V) 2 Poles in Series, 70 °C 22 A(110 V) 3 Poles in Series, 40 °C 25 A(110 V) 3 Poles in Series, 60 °C 25 A(110 V) 3 Poles in Series, 70 °C 22 A(220 V) 2 Poles in Series, 40 °C 10 A(220 V) 2 Poles in Series, 60 °C 10 A(220 V) 2 Poles in Series, 70 °C 10 A(220 V) 3 Poles in Series, 40 °C 25 A(220 V) 3 Poles in Series, 60 °C 25 A(220 V) 3 Poles in Series, 70 °C 22 A(72 V) 1-Pole, 40 °C 25 A(72 V) 1-Pole, 60 °C 25 A(72 V) 1-Pole, 70 °C 22 A(72 V) 2 Poles in Series, 40 °C 25 A(72 V) 2 Poles in Series, 60 °C 25 A(72 V) 2 Poles in Series, 70 °C 22 A(72 V) 3 Poles in Series, 40 °C 25 A(72 V) 3 Poles in Series, 60 °C 25 A(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 6 A(110 V) 1-Pole, 60 °C 6 A(110 V) 1-Pole, 70 °C 6 A(110 V) 2 Poles in Series, 40 °C 25 A(110 V) 2 Poles in Series, 60 °C 25 A(110 V) 2 Poles in Series, 70 °C 22 A(110 V) 3 Poles in Series, 40 °C 25 A(110 V) 3 Poles in Series, 60 °C 25 A(110 V) 3 Poles in Series, 70 °C 22 A(220 V) 2 Poles in Series, 40 °C 6 A(220 V) 2 Poles in Series, 60 °C 6 A(220 V) 2 Poles in Series, 70 °C 6 A(220 V) 3 Poles in Series, 40 °C 25 A(220 V) 3 Poles in Series, 60 °C 25 A(220 V) 3 Poles in Series, 70 °C 22 A(72 V) 1-Pole, 40 °C 25 A(72 V) 1-Pole, 60 °C 25 A(72 V) 1-Pole, 70 °C 22 A(72 V) 2 Poles in Series, 40 °C 25 A(72 V) 2 Poles in Series, 60 °C 25 A(72 V) 2 Poles in Series, 70 °C 22 A(72 V) 3 Poles in Series, 40 °C 25 A(72 V) 3 Poles in Series, 60 °C 25 A(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A(110 V) 1-Pole, 60 °C 4 A(110 V) 1-Pole, 70 °C 4 A(110 V) 2 Poles in Series, 40 °C 10 A(110 V) 2 Poles in Series, 60 °C 10 A(110 V) 2 Poles in Series, 70 °C 10 A(110 V) 3 Poles in Series, 40 °C 25 A(110 V) 3 Poles in Series, 60 °C 25 A(110 V) 3 Poles in Series, 70 °C 22 A(220 V) 2 Poles in Series, 40 °C 4 A(220 V) 2 Poles in Series, 60 °C 4 A(220 V) 2 Poles in Series, 70 °C 4 A(220 V) 3 Poles in Series, 40 °C 9 A(220 V) 3 Poles in Series, 60 °C 9 A(220 V) 3 Poles in Series, 70 °C 9 A(72 V) 1-Pole, 40 °C 9 A(72 V) 1-Pole, 60 °C 9 A(72 V) 1-Pole, 70 °C 9 A(72 V) 2 Poles in Series, 40 °C 25 A(72 V) 2 Poles in Series, 60 °C 25 A(72 V) 2 Poles in Series, 70 °C 22 A(72 V) 3 Poles in Series, 40 °C 25 A(72 V) 3 Poles in Series, 60 °C 25 A(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 Vacc. to IEC 60947-5-1 690 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.75 ... 6 mm²Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Rigid Solid 1/2x 1 ... 4 mm²Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mmControl Circuit 10 mmMain Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type
Screw Terminals

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3706210
E-Number (Sweden)
3210005

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations acc. to IEC 60068-2-6
5 ... 300 Hz 4 g closed position / 2 g open position
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 gOpen, Shock Direction: B1 5 gShock Direction: A 30 gShock Direction: B2 15 gShock Direction: C1 25 gShock Direction: C2 25 g
RoHS Status
Following EU Directive 2011/65/EU

Technical UL/CSA

NEMA Size
00
Continuous Current Rating NEMA
9 A
Horsepower Rating NEMA
(115 V AC) Single Phase 1/3 Hp(200 V AC) Three Phase 1-1/2 Hp(230 V AC) Single Phase 1 Hp(230 V AC) Three Phase 1-1/2 Hp(460 V AC) Three Phase 2 Hp(575 V AC) Three Phase 2 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 25 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3/4 hp(200 ... 208 V AC) Three Phase 2 hp(220 ... 240 V AC) Three Phase 2 hp(240 V AC) Single Phase 1-1/2 hp(440 ... 480 V AC) Three Phase 5 hp(550 ... 600 V AC) Three Phase 7-1/2 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWGRigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lbControl Circuit 11 in·lbMain Circuit 13 in·lb

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900

Related products

EA1812 ABB, Other
EA1812
ABB
IS2-EA1812 Control and Automation Board
EC1881K ABB, Other
EC1881K
ABB
IS2-EC1881K Control and Automation Board
1SFA616922R1028 ABB, Lighting
1SFA616922R1028
ABB
KA3-1028 Filament Bulb
MI1400 ABB, Control Cabinets
MI1400
ABB
L-MI1400 Cabinet, 1420 mm x 140 mm x 50 mm
S403M-B32NP ABB, Power Supply
S403M-B32NP
ABB
S403M-B32NP Miniature Circuit Breaker
EXN05AC5 ABB, Other
EXN05AC5
ABB
3/4NPT N/P BRASS BAR GLAND16-21MM
OT63F3 ABB, Switches
OT63F3
ABB
SWITCH
OTPL125FD ABB, Other
OTPL125FD
ABB
EMK/LBRK N-POLE OT30-125 DR MT
OVRT270NCU ABB, Other
OVRT270NCU
ABB
SPD, OVR, 70KA,NEUTRAL, CARTRIDGE
OZXA-800 ABB, Other
OZXA-800
ABB
OT/OS600 OS800 TERM KIT QTY 6/BAG
RV-BC6/250 ABB, Other
RV-BC6/250
ABB
SUPRESSOR, SURGE, VARISTOR,
1SDA070842R1 ABB, Circuit Breakers
1SDA070842R1
ABB
E1.2N 1250 Ekip Dip LSI 3p F F