Weidmuller

1202540000

1 / 2
thumbnail
thumbnail

Description

Power supply, switch-mode power supply unit
Part Number
1202540000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

General Data

AC failure bridging time @ I
min. 20 ms
Ambient temperature
-20°C...70°C (>50°C derating,refer derated curve); 70% rated load @ 70°C
Degree of efficiency
83 % @ 48 V DC
EMC standards
EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3
Indication
Operation, green LED
Max. perm. air humidity (operational)
5 %…95 % RH
Mounting position, installation notice
Panel mount, screw fix
Protection degree
IP20
Short-circuit protection
Yes
Standards
EN 60950

Connection Data (Input)

Connection system
Screw connection

Approvals

Approvals
CE, cURus, EAC
ROHS
Conform
UL File Number Search
E349964

Dimensions And Weights

Width
115 mm
Width (inches)
4.528 inch
Height
49.5 mm
Height (inches)
1.949 inch
Depth
231 mm
Depth (inches)
9.094 inch
Net weight
1,052 g

Electrical Safety (Applied Standards)

Safety extra-low voltage
SELV according to EN 60950

Rated Data Ul

Certificate No. (cURus)
E349964

Emc / Shock / Vibration

Noise emission in accordance with EN55032
Class A

Input

AC current consumption
2.5 A @ 230 V AC / 4.7 A @ 120 V AC
AC input voltage range
88...132 V AC / 176...264 V AC optional
Connection system
Screw connection
DC input voltage range
250...370 V DC
Frequency range AC
47...63 Hz
Input fuse (internal)
yes / max. 35A
Rated input voltage
100...240 V AC (wide-range input)
Recommended back-up fuse
6 A at 230 V AC, characteristic curve C

Classifications

ETIM 6.0
EC002540
ETIM 7.0
EC002540
EClass 9.0
27-04-07-01
EClass 9.1
27-04-07-01
EClass 10.0
27-04-07-01

Output

Mains failure bridge-over time
20 ms
Output current
5.2 A@48 V DC
Output power
250 W
Output voltage
± 10% nominal output voltage tolerance, adjustable with potentiometer
Overload protection
120~150% Ikonst. of max. output power, automatic restart
Parallel connection option
Recommended with diode module
Rated output voltage
48 V DC
Residual ripple, breaking spikes
< 100 mVPP
Surge protection
55...62 V @ 48 V DC

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

System Data

Output current
5.2 A@48 V DC

Insulation Coordination

Electrical isolation, input-earth
2 kV
Electrical isolation, input-output
3 kV
Electrical isolation, output-earth
0.5 kV

Temperatures

Storage temperature, max.
85 °C
Storage temperature, min.
-20 °C
Ambient temperature
-20°C...70°C (>50°C derating,refer derated curve); 70% rated load @ 70°C
Storage temperature