Fluke

1738/EUS

1 / 4
thumbnail
thumbnail
thumbnail
thumbnail
Part Number
1738/EUS
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Current Inputs

Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Range
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
Input voltage
Clamp input: 500 mVrms/50 mVrms; CF 2.8
Range
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
Range
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
Number of inputs
4, mode selected automatically for attached sensor
Scaling
1:1 and variable
Range
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Rogowski coil input
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range

Wireless Connection

Number of inputs
2
Supported modules
Fluke Connect® 3000 series
Acquisition
1 reading/s

Data Acquisition

Memory size
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
Input signal frequency
50/60 Hz (42.5 to 69 Hz)
Memory size
¹The number of possible logging sessions and logging period depends on user requirements.
Sampling frequency
10.24 kHz at 50/60 Hz, synchronized to mains frequency
Data storage
Internal flash memory (not user replaceable)
Circuit types
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Resolution
16-bit synchronous sampling

Auxiliary Inputs

Input range
0 to ±10 V dc, 1reading/s
Number of inputs
2
Displayed units (available 2014)
User configurable (7 characters, for example, °C, psi, or m/s)
Scale factor (available 2014)
Format: mx + b (gain and offset) user configurable

Standards Compliance

Harmonics
IEC 61000-4-7: Class 1
Power quality compliance
EN50160 (for measured parameters)
Power quality
IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power
IEEE 1459
Harmonics
IEEE 519 (short time harmonics)

Voltage Inputs

Measurement category
1000 V CAT III/600 V CAT IV
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Input impedance
10 MΩ
Scaling
1:1 and variable
Maximum input voltage
1000 Vrms, CF 1.7
Number of inputs
4 (3 phases and neutral)

Basic Interval

Measured parameters
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging time min/max values
Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Averaging interval
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min

Interfaces

USB-A
File transfer via USB flash drive, firmware updates Max. current: 120 mA
Bluetooth
Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
WiFi
File transfer and remote control via direct connection or WiFi infrastructure
USB-mini
Data download device to PC

Environmental Specifications

Safety
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Safety
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
Vibration
MIL-T-28800E, Type 3, Class III, Style B
Temperature coefficient
0.1 x accuracy specification/°C
Operating altitude
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage temperature
-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
Operating temperature
-10 °C to +50 °C (14 °F to 122 °F)
Operating humidity
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Safety
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Storage altitude
12,000m
Electromagnetic compatibility
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Electromagnetic compatibility
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Electromagnetic compatibility
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
Operating humidity
10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
Enclosure
IP50 in accordance with EN60529
Safety
IEC 61010-1

Electrical Specifications

Efficiency
≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption
< 0.3 W only when powered using IEC 60320 input
Battery
Li-ion 3.7 V, 9.25 Wh, customer-replaceable
Mains power frequency
50/60 Hz ±15%
Voltage range
100 V to 500 V using safety plug input when powering from the measurement circuit
On-battery runtime
Four hours in standard operating mode, up to 5.5 hours in power saving mode
Voltage range
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Charging time
< 6 hours

Power Quality Measurements

Triggered recordings
Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Measured parameter
Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Individual harmonics
2nd to 50th harmonic
Events
Voltage: dips, swells, interruptions, current: inrush current
Total harmonic distortion
Calculated on 50 harmonics
Triggered recordings
Waveform of voltage and current
Averaging interval
10 min

Demand Interval (Energy Meter Mode)

Measured parameters
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off

General Specifications

Dimensions
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Dimensions
Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Warranty
Accessories: one-year
Warranty
Calibration cycle: two-years
Weight
Power supply: 400 g (0.9 lb)
Dimensions
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Color LCD display
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Weight
Instrument: 1.1 kg (2.5 lb)
Tamper protection
Kensington lock slot
Warranty
Instrument and power supply: Two-years (battery not included)

i17xx-flex 1500 12" Flexible Current Probe Specifications

Output cable
TPR/PVC
Measuring range
1 to 150 A ac/10 to 1500 A ac
Intrinsic error at reference condition*
±0.7% of reading
Output cable length
2 m (6.6 ft)
Working voltage
1000 V CAT III, 600 V CAT IV
Operating temperature
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Probe cable diameter
7.5 mm (0.3 in)
Warranty
Reference condition: Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65% Primary conductor in center position
Probe cable length
305 mm (12 in)
Probe cable material
TPR
Nondestructive current
100 kA (50/60 Hz)
Coupling material
POM + ABS/PC
Temperature, non-operating
-40 °C to +80 °C (-40 °F to 176 °F)
Warranty
One-year
Temperature coefficient over operating temperature range
0.05% of reading/°C 0.09% of reading/°F
Minimum bending radius
38 mm (1.5 in)
Accuracy 173x + iFlex
±(1% of reading + 0.02% of range)
Relative humidity, operating
15% to 85% non-condensing
Weight
115 g
IP rating
IEC 60529:IP50