Fluke

1738/WINTL

1 / 4
thumbnail
thumbnail
thumbnail
thumbnail
Part Number
1738/WINTL
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Current Inputs

Range
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
Range
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
Number of inputs
4, mode selected automatically for attached sensor
Range
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
Rogowski coil input
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Scaling
1:1 and variable
Input voltage
Clamp input: 500 mVrms/50 mVrms; CF 2.8
Range
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz

Wireless Connection

Supported modules
Fluke Connect® 3000 series
Number of inputs
2
Acquisition
1 reading/s

Data Acquisition

Data storage
Internal flash memory (not user replaceable)
Sampling frequency
10.24 kHz at 50/60 Hz, synchronized to mains frequency
Resolution
16-bit synchronous sampling
Input signal frequency
50/60 Hz (42.5 to 69 Hz)
Memory size
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
Memory size
¹The number of possible logging sessions and logging period depends on user requirements.
Circuit types
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)

Auxiliary Inputs

Number of inputs
2
Input range
0 to ±10 V dc, 1reading/s
Scale factor (available 2014)
Format: mx + b (gain and offset) user configurable
Displayed units (available 2014)
User configurable (7 characters, for example, °C, psi, or m/s)

Standards Compliance

Harmonics
IEEE 519 (short time harmonics)
Power
IEEE 1459
Power quality
IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power quality compliance
EN50160 (for measured parameters)
Harmonics
IEC 61000-4-7: Class 1

Voltage Inputs

Scaling
1:1 and variable
Maximum input voltage
1000 Vrms, CF 1.7
Input impedance
10 MΩ
Number of inputs
4 (3 phases and neutral)
Measurement category
1000 V CAT III/600 V CAT IV
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz

Basic Interval

Measured parameters
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging time min/max values
Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Averaging interval
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min

Interfaces

USB-A
File transfer via USB flash drive, firmware updates Max. current: 120 mA
Bluetooth
Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
WiFi
File transfer and remote control via direct connection or WiFi infrastructure
USB-mini
Data download device to PC

Environmental Specifications

Electromagnetic compatibility
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
Storage temperature
-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Safety
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Safety
IEC 61010-1
Temperature coefficient
0.1 x accuracy specification/°C
Vibration
MIL-T-28800E, Type 3, Class III, Style B
Operating humidity
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Safety
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
Electromagnetic compatibility
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Enclosure
IP50 in accordance with EN60529
Operating humidity
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
Operating temperature
-10 °C to +50 °C (14 °F to 122 °F)
Operating altitude
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Safety
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Operating humidity
10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
Storage altitude
12,000m

Electrical Specifications

On-battery runtime
Four hours in standard operating mode, up to 5.5 hours in power saving mode
Mains power frequency
50/60 Hz ±15%
Battery
Li-ion 3.7 V, 9.25 Wh, customer-replaceable
Voltage range
100 V to 240 V using standard power cord (IEC 60320 C7)
Maximum no-load consumption
< 0.3 W only when powered using IEC 60320 input
Efficiency
≥ 68.2% (in accordance with energy efficiency regulations)
Charging time
< 6 hours
Voltage range
100 V to 500 V using safety plug input when powering from the measurement circuit
Power consumption
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)

Power Quality Measurements

Triggered recordings
Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Measured parameter
Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Averaging interval
10 min
Total harmonic distortion
Calculated on 50 harmonics
Events
Voltage: dips, swells, interruptions, current: inrush current
Individual harmonics
2nd to 50th harmonic
Triggered recordings
Waveform of voltage and current

Demand Interval (Energy Meter Mode)

Interval
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Measured parameters
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy

General Specifications

Warranty
Calibration cycle: two-years
Weight
Instrument: 1.1 kg (2.5 lb)
Dimensions
Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Color LCD display
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty
Accessories: one-year
Weight
Power supply: 400 g (0.9 lb)
Dimensions
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Tamper protection
Kensington lock slot
Dimensions
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Warranty
Instrument and power supply: Two-years (battery not included)

i17xx-flex 1500 12" Flexible Current Probe Specifications

Warranty
Reference condition: Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65% Primary conductor in center position
Temperature, non-operating
-40 °C to +80 °C (-40 °F to 176 °F)
Probe cable material
TPR
Working voltage
1000 V CAT III, 600 V CAT IV
Probe cable diameter
7.5 mm (0.3 in)
Coupling material
POM + ABS/PC
Probe cable length
305 mm (12 in)
Measuring range
1 to 150 A ac/10 to 1500 A ac
Temperature coefficient over operating temperature range
0.05% of reading/°C 0.09% of reading/°F
Relative humidity, operating
15% to 85% non-condensing
Minimum bending radius
38 mm (1.5 in)
Nondestructive current
100 kA (50/60 Hz)
Accuracy 173x + iFlex
±(1% of reading + 0.02% of range)
Output cable
TPR/PVC
IP rating
IEC 60529:IP50
Output cable length
2 m (6.6 ft)
Warranty
One-year
Intrinsic error at reference condition*
±0.7% of reading
Operating temperature
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Weight
115 g