Fluke
1760TR
1 / 1
- Part Number
- 1760TR
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Features
- Fully Class-A compliant:
- Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard
- GPS time synchronization:
- Correlate data with events or datasets from other instruments with precision
- Flexible and fully configurable thresholds and scale factors:
- Allows user to pinpoint specific issues by defining the detailed criteria for detection and recording of disturbances.
- Uninterrupted power supply (40 minutes):
- Never miss important events - even record the beginning and end of interruptions and outages to help determine the cause
- 10 MHz, 6000 Vpk waveform capture:
- Get a detailed picture of even the shortest event
- 2 GB data memory:
- Enables detailed, simultaneous recording of numerous power parameters for long periods of time
- Comprehensive software included:
- Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring in the online mode
- Plug and play:
- Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries
- Rugged field design:
- Insulated housing and a solid state design with no rotating components enable reliable testing under nearly any conditions
Uncertainties
- Reference conditions
- Warmed up instrument > 3 h
- Temperature drift
- Change of amplification through temperature: < 0.005%/K
- Reference conditions
- 23°C ±2 K < 60% rH; 74°F ±2 K < 60% rH
- With Sensor 1000 V
- 0,1% at Udin = 480 V and 600 V P-N
- Sensor 600 V
- 0,1% at Udin = 230 V P-N
- Intrinsic uncertainty for harmonics
- Class I as per EN 61000-4-7:2002
- Aging
- Change of amplification due to ageing: < 0.04%/year
- Noise
- Noise voltage, input short-circuited: < 40 µV
- Temperature drift
- 100 ppm / K
- DC
- ±(0.2% rdg + 0.1% sensor)
- Reference conditions
- Power supply: 100 V to 250 V AC
- Aging
- < 0.05% / year
- Uncertainty at reference conditions
- Uncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
- Common mode rejection
- > 100 dB at 50 Hz
Signal Conditioning
- Uncertainty for frequency measurements
- < 20 ppm
- Resolution
- 16 ppm
- Uncertainty of internal clock
- < 1 s/day
- Range for 50 Hz systems
- 50 Hz ±15% (42.5 Hz to 57.5 Hz)
- Flicker
- as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
- Measurement intervals
- Aggregation of the interval values as per IEC 61000-4-30 Class-A
- Harmonics
- as per IEC 61000-4-7:2002: 200 ms
- Min-, Max-values
- Half cycle, e.g.: 10 ms rms values at 50 Hz
- Sampling frequency for 50 Hz power frequency
- 10.24 kHz, The sampling rate is synchronized to mains frequency.
- Range for 60 Hz systems
- 60 Hz ±15% (51 Hz to 69 Hz)
- Transients
- Sample rate 100 kHz to 10 MHz per channel
Class-A Compliance For The Most Demanding Power Quality Tests
- Detailed disturbance analysis
- – Perform high-speed transient analysis and uncover root cause of equipment malfunction for later mitigation and predictive maintenance. The fast transient option, with its 6000 V measurement range, allows capture of very short impulses such as lightning strikes.
- Class-A quality-of-service compliance
- – Validate incoming power quality at the service entrance. Thanks to Class A compliance, the Fluke 1760 allows undisputable verification.
- Event correlation at multiple locations
- – Utilizing GPS time synchronization, users can quickly detect where a fault occurred first, either inside or outside the facility.
- Galvanic separation and DC coupling
- – Allows complete measurements on dissimilar power systems. For example troubleshoot UPS systems by simultaneously recording the battery voltage and power output.
- Power quality and power load studies
- – Assess baseline power quality to validate compatibility with critical systems before installation and verify electrical system capacity before adding loads.
Measurement Inputs
- Range (peak value)
- 280 mV
- Nominal voltage (rms)
- 100 mV
- Basic safety
- 300 V CAT III
- Input filter
- Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse. The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.
- Input capacitance
- 5 pF
- Input resistance
- 1 MΩ
- Overload capacity (rms)
- 1000 V, continuously
- Number of inputs
- 8 galvanically isolated inputs for voltage and current measurements.
- Voltage rise rate
- max. 15 kV / µs
- Sensor safety
- up to 600 V CAT IV depending on sensor
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther