1 / 1
thumbnail

Description

This Micrologic 5.0 X is an electronic control unit used on Masterpact MTZ1, MTZ2 and MTZ3 fixed circuit breakers. This control unit is compatible with MTZ1 06 to MTZ1 16, MTZ 08 to MTZ2 40, MTZ3 40 to MTZ3 63, all in fixed version. Masterpact MTZ is the last generation of high current air circuit breakers up to 6300 A embedding advanced digital technologies. Masterpact MTZ is designed to protect electrical systems from damage caused by overloads, short circuits and equipment ground faults. It is possible to customize Micrologic X control unit anytime with digital modules to add new protection, measurement or diagnosis functionalities. Micrologic X control units incorporate several channels of communication, including Ethernet, Modbus SL and wireless communication facilities. Micrologic 5.0 X embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. With its embedded backlight HMI, Micrologic 5.0 X allows the quick identification of alarm messages. The information processed by the Micrologic 5.0 X may be displayed on the embedded backlight HMI, a smartphone through Bluetooth or NFC and a PC through the USB connection. The protections can be set by means of the embedded display, a smartphone via Bluetooth or with a PC running EcoStruxure Power Commission, and additionally via Ethernet and Modbus SL communication. Masterpact MTZ and Micrologic X are part of EcoStruxure architecture system.
Country of Origin
FR
Part Number
LV847283
Tariff Code
85363090
EAN
3606480811241
UNSPSC
39121601
Payment methods:
Best offer from:
FRTrusted Automa.Net Supplier
Availability:
2 pcs.
In-Stock
Updated at: 08-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
A total of 4 Parts In-Stock from 2 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (1)

LV847283 product image
Schneider Electric

LV847283

Condition:
New Surplus
Available:
2 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€799.58

Specifications

Network Frequency
50/60 Hz
Trip Unit Protection Functions
LSI
Network Type
AC
[Ue] Rated Operational Voltage
690 V AC, +/- 10 %
Range Compatibility
MasterPact (MasterPact MTZ1) circuit breaker || MasterPact (MasterPact MTZ2) circuit breaker || MasterPact (MasterPact MTZ3) circuit breaker || MasterPact (MasterPact MTZ2 H10) circuit breaker
Protected Poles Description
3P 3d || 4P 3d || 4P 3d + N/2 || 4P 4d || 4P 3d + OSN
Trip Unit Rating
400-400 A || 630-630 A || 800-800 A || 1000-1000 A || 1250-1250 A || 1600-1600 A || 2000-2000 A || 2500-2500 A || 3200-3200 A || 4000-4000 A || 5000-5000 A || 6300-6300 A
Product Or Component Type
control unit
Range
MasterPact
Circuit Breaker Application
distribution IEC standard
Poles Description
3P || 4P
Protection Type
overload protection (long time) ANSI 49 || instantaneous short-circuit protection ANSI 50 || short time short-circuit protection ANSI 51
Device Application
equipment protection, monitoring and control
Device Short Name
Micrologic 5.0 X
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

Measurement Voltage
145.6-828 V AC 50/60 Hz per phase
Thermal Memory
yes
Frequency Measurement Range
45-250 Hz
Type Of Measurement
power meter
Long Time Pick-Up Adjustment Range
0.4...1 x In adjustable in step of 1 A
Communication Port Protocol
Bluetooth 4.0 LE peer to peer 30 kbit/s || NFC peer to peer ISO 15963 || USB peer to peer 115 kbauds
Display Type
LCD display - 128 x 96 pixels
Long Time Delay Adjustment Type
adjustable in step of 0.5 s
Instantaneous Pick-Up Adjustment Type Ii
adjustable
Zone Selective Interlocking Zsi
with
Metering Type
current I1, I2, I3, In, Ig maximum standard) || average voltage Vavg standard) || active power P, P1, P2, P3 standard) || reactive power Q, Q1, Q2, Q3 standard) || apparent power S, S1, S2, S3 standard) || power factor standard) || frequency standard) || total current harmonic distortion THD (I) inst, avg, avg min, avg max fundamental voltage standard) || total current harmonic distortion THD (I) inst, avg, avg min, avg max RMS voltage standard) || voltage V21, V32, V13, V1, V2, V3 instantaneous standard) || voltage V21, V32, V13, V1, V2, V3 minimum standard) || voltage V21, V32, V13, V1, V2, V3 maximum standard) || total voltage harmonic distortion THD (V) inst, avg, avg min, avg max fundamental voltage standard) || total voltage harmonic distortion THD (V) inst, avg, avg min, avg max RMS voltage standard) || demand current I1, I2, I3, In, Iavg standard) || demand power P, Q, S standard)
[Tr] Long-Time Delay Adjustment Range
12.5-600 s 1.5 x Ir || 0.5-24 s 6 x Ir || 0.7-16.6 s 7.2 x Ir
Short-Time Delay Adjustment Type
adjustable
Neutral Protection Setting
1 x Ir || 0.5 x Ir || 1.6 x Ir || no protection
Instantaneous Pick-Up Adjustment Range
2...15 x In adjustable in step of 0.5 x In embedded HMI || 2...15 x In adjustable in step of 0.1 x In Ecoreach software or MasterPact MTZ mobile app || Ii enable on/off
Operating Time
0 ms fast || 20 ms standard
Mounting Mode
fixed
[Tsd] Short-Time Delay Adjustment Range
0.1-0.4 s I²t=on || 0-0.4 s I²t=off
Measurement Accuracy
power factor +/- 1 % || active energy Ep IN/OUT/tot +/- 1 % - 10...10 GWh || reactive energy Ep IN/OUT/tot +/- 2 % - 10...10 GVARh || apparent energy Es IN/OUT/tot +/- 1 % - 10...10 GVAh || unbalance current +/- 0.5 % || frequency +/- 0.005 Hz || voltage V21, V32, V13, VLLavg +/- 0.5 % 208...690 x 1.2 V || voltage V21, V32, V13, VLNavg +/- 0.5 % 120...400 x 1.2 V || apparent power S, S1, S2, S3, Sdemand +/- 1 % || active power P, P1, P2, P3, Pdemand +/- 1 % || reactive power Q, Q1, Q2, Q3, Qdemand +/- 2 % || current I1, I2, I3, Iavg, Idemand for MTZ1 +/- 0.5 % 40...1600 x 1.2 A || current I1, I2, I3, Iavg, Idemand for MTZ2 +/- 0.5 % 40...4000 x 1.2 A || current I1, I2, I3, Iavg, Idemand for MTZ3 +/- 0.5 % 80...6300 x 1.2 A
Data Recording
data logs || time stamping || alarm logs || min/max of instantaneous values || event logs || maintenance logs
Network And Machine Diagnosis Type
system (HMI) health state overview circuit breaker health state standard) || contacts state circuit breaker health state standard) || micrologic service life circuit breaker health state standard) || tripping cause indication circuit breaker tripping cause standard) || identification card diagnostic data standard) || configured alarms synthesis diagnostic data standard) || monitored function diagnostic data standard) || operation diagnostic data standard) || micrologic test test standard) || protection test test standard) || selectivity test test standard) || trip context information crisis management standard) || operation advanced diagnostic standard) || breaker service life circuit breaker health state standard)
Energy Management
measurement ,active, reactive and apparent energy (standard) || measurement ,electrical network (standard) || measurement ,energy (standard)
[Isd] Short-Time Pick-Up Adjustment Range
1.5...10 x Ir adjustable in step of 0.5 x Ir embedded HMI || 1.5...10 x Ir adjustable in step of 0.1 x Ir Ecoreach software or MasterPact MTZ mobile app
Accuracy Class
class 5 total current harmonic distortion THD (I) || class 0.5 unbalance voltage || class 1 active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) || class 2 total voltage harmonic distortion THD (V)

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1607009EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1607009EN
Eu Rohs Directive
Compliant
Halogen Content Performance
Halogen free plastic parts product

Environment

Standards
EN/IEC 60947-1 || EN/IEC 60092-202 || EN/IEC 60947-2 || EN/IEC 60255-1 || EN/IEC 61010-1
Ambient Air Temperature For Operation
-25-70 °C operating) || -35--35 °C for start-up of product)
Electromagnetic Compatibility
electrostatic discharge immunity test IEC 61000-4-2 || susceptibility to electromagnetic fields IEC 61000-4-3 || electrical fast transient/burst immunity test IEC 61000-4-4 || 1.2/50 µs shock waves immunity test IEC 61000-4-5 || conducted RF disturbances IEC 61000-4-6 || conducted and radiated emissionsA CISPR 22
Environmental Characteristic
wet location not approved for use IEC 61010-1
Mounting Location
indoor use only
Pollution Degree
3 IEC 60947-1
Overvoltage Category
IV IEC 61010-1
Relative Humidity
95-95 % 55-55 °C IEC 60068-2-30
Operating Altitude
<= 6561.68 ft (2000 m) without derating || <= 13123.36 ft (4000 m) with operational voltage derating 600 V AC || <= 16404.2 ft (5000 m) with operational voltage derating 560 V AC
Measurement Category
category IV IEC 61010-2-30