1 / 1
thumbnail

Description

Active Mature
TeSys GV electrical trip unit, MX shunt trip, 380-415V AC 50Hz / 440-480V AC 60Hz, for motor circuit breakers GV4. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be plugged inside the circuit breaker, connection by spring terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Country of Origin
FR
Part Number
GV4AS487
Tariff Code
85363010
EAN
3606485444925
UNSPSC
39121010
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

[Uc] Control Circuit Voltage
440...480 V AC 60 Hz || 380...415 V AC 50 Hz
Range Compatibility
TeSys TeSys GV4 || TeSys TeSys BV4
Product Or Component Type
voltage release
Range
TeSys
Voltage Release Type
shunt trip release
Device Application
control
Device Short Name
MX

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2311043EN
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2311043EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Maximum Inrush Power In Va
6 VA
Connections - Terminals
spring terminals 1 0.5-1.5 mm² - cable stiffness: flexible without cable end
Wire Stripping Length
8 mm
[Ui] Rated Insulation Voltage
480 V IEC 60947-1
Impulse Duration
>= 20 ms
Mounting Mode
internal mounting
Mechanical Durability
20000 cycles
Maximum Hold-In Power Consumption In Va
10 VA
Threshold Tripping Voltage
0.7...1.1 Un failsafe opening || < 0.7 Un possible opening
Operating Time
< 50 ms

Environment

Quantity Per Set
set of 1

CAD Models